Service Diagnosis

No Ice

Problem

Likely Cause

Probable Solution

No power to unit

Power disconnected

Check breaker or fuse. Reset or
replace, restart and check

No power to controller

Transformer open

Replace transformer

Control panel open

Switch failure

Test ribbon cable, see page 32

Shut down on maximum
water fill time - water light
flashing

Water shut off

Restore water supply

Very long freeze cycle

Water leak

Check curtain, sump

Dirty condenser

Clean condenser

Restricted location, intake air too
hot or blocked

Eliminate restriction, have machine
moved

Evaporator thermistor not sensing
properly

Check thermistor

Spray jets dirty

Remove spray platform and clean
spray jets

Inlet water valve leaks through
during freeze

Check inlet water valve

Low on refrigerant

Check cube formation,

Connected to hot water

Check for bleed thru from missing /
broken check valve in building
water supply

Cannot make ice

Spray pump not pumping

Check pump motor

Fan motor not turning

Check fan motor, check fan blade,
check controller for voltage output

Pump hose disconnected

Check hose

Very low on refrigerant

Add access valve, add refrigerant
as a test. If unit makes ice, find and
correct leak.

Compressor not operating

Check compressor start
components, check PTCR
resistance and temperature

Check compressor voltage

Check compressor windings

Hot gas valve leaks through during
freeze

Check hot gas valve for hot outlet
during freeze

Compressor inefficient

Check compressor amp draw, if low
and all else is correct, change
compressor

January 2012

Page 26