Sccg50 & sccp50 service manual – Scotsman SCCG50 User Manual

Page 33

Advertising
background image

Refrigeration Service

This ice machine use R-134a type refrigerant.
There are specific rules for handling that
refrigerant.

To check for system pressures, add a field supplied
clamp-on type service valve as a temporary means
of system access. After diagnosis and before final
repair, replace the clamp-on type valve with valves
that are brazed onto the process tubes of the
system.

Use a low flow of dry nitrogen when brazing on the
system.

Install a new filter drier when replacing a
refrigeration component or after a refrigerant leak
repair.

Evacuate the system to at least 300 microns and
use a micron gauge to measure the evacuation
level.

Weigh in the nameplate charge. The machine is
critically charged and a partial ounce mis-charge
will affect performance.

January 2012

Page 32

SCCG50 & SCCP50

Service Manual

Membrane Switch

Unplug and check connector pins (left side from
front is pin 1), read about 10 ohms when activating
the button, and OL when not pressing the button:
Pin 2-3 On/Off Switch; 4-3 Clean Reset Switch

Bin Thermostat Altitude Adjustment Table

Altitude

Degrees Rotation to Turn
Adjustment Screw

1000

11 CW

2000

31 CW

3000

52 CW

4000

72 CW

5000

92 CW

6000

111 CW

7000

128 CW