Appendix A – e-TRIM Modbus Registers

The following list is a description of the relevant Modbus registers in the e-TRIM system. For

communications, the e-TRIM supports Modbus on the Host 485 port and ModbusTCP through

Ethernet.

11

Active burner bitmap

14

Modbus address

15

Master Setpoint (2 decimal places)

16

Deviation alarm band setpoint (2 decimal places)

17

Out of band alarm delay time

18

Alarm disable bitmap

19

Alarm bitmap, burners 1 - 16.

20 - 35

O

2

readings, sensors 1 - 16, 2 decimal places.

68 - 83

High Fire ON, sensors 1 - 16.

116 - 131

O

2

trim delay, sensors 1 - 16.

132 - 147

O

2

trim interval time, sensors 1 - 16.

148 - 163

O

2

alarm state, sensors 1 - 16.

0 = normal, 1 = bad communications, 2 = out of and pending, 3 = out

of band.

164 - 179

Alarm delay timer (sec), sensors 1 = 16.

180 - 195

O

2

offset, sensors 1 - 16.

220 - 235

Slave communications status, boards 1 - 16. 0 = bad

communications, 4 = OK.

460

Critical alarm bitmap

461 - 476

Critical alarm, sensors 1 - 16.

477 - 492

Critical alarm set point, sensors 1 - 16.

493

Critical alarm acknowledge. 1 = acknowledged.

600

High fire total time (sec), sensor 1

601

High fire total time (hr), sensor 1

602

Low fire total time (sec), sensor 1

603

Low fire total time (hr), sensor 1

604

High fire timer, sensor 1

605

Low fire timer sensor 1

606 - 611

Timers for Sensor 2

612 - 617

Timers for sensor 3

618 - 623

Timers for sensor 4

624 - 629

Timers for sensor 5

630 - 635

Timers for sensor 6

636 - 641

Timers for sensor 7

642 - 647

Timers for sensor 8