6 relay output wiring – Tecfluid MT03F User Manual

Page 11

Advertising
background image

11

3.2.6 Relay

output

wiring

Terminal

Description

Relay

13

Normally open

Relay 1

14

Normally closed

Relay 1

15

Common

Relay 1

16

Normally open

Relay 2

17

Normally closed

Relay 2

18

Common

Relay 2

The relay outputs provide relays with potential free contacts (see characteristics on page
37).

The status of the relay contacts corresponds to the relay at rest

.

The relay contacts are not protected in any way, and therefore they must be installed
externally

as required in the application

, taking into account the limitations of the

characteristics of such contacts.
In the case of having inductive loads, and to extend the working life of the relay contacts,
it is recommended to use overvoltage protection (VDR for AC and diodes for DC loads).
In all cases a fuse or some kind of protection against short circuits

should always be

provided

according to the needs of the intended load.

Advertising