Pcs-com in-line and t-splice kit, Power connection for flx-bc with braid only – Thermon PCS-COM User Manual

Page 5

Advertising
background image

4

3.3.

Feed cable and ground through expediter

base as shown. Feed cable and ground

lead through grommet (above the crimp).

3.2.

Trim braid to approximately 76mm (3”).

Crimp 12/10 AWG compression lug to
ground braid and ground lead.

3.1.

Separate braid strands at edge of overjacket

and pull cable through opening.

Ground Lead Wire

12/10 AWG

Crimp

Expediter

Base

Grommet

Ground

Lead

Cable

152mm

(6”)

Power connection for FLX-BC with braid only.

76mm

(3”)

Braid

3.4.

Slide expediter toward pipe and secure

using two (2) circumferential bands of
19mm (3/4”) wide tape.

3.5.

Place UL® label provided as shown,

locate on opposite side from rectangular

side opening.

Pip

e H

ea

tin

g C

ab

le 1

34

N

HS

X

® or

FL

X™

H

ea

tin

g C

ab

le S

ys

tem

Ins

tall

C

ab

le p

er N

EC

A

rti

cle

42

7

Th

erm

on

M

an

ufactu
rin

g C

o.

10

0

Th

erm

on

D

r., San Marco

s,

Te

xas 7866

6

1-8

00

-7

30

-4

32

8

P

N

2

74

00

Tape Provided

Separately

UL Label

3.6.

Cut and remove primary insulation jacket.

3.7.

Skive outside of black matrix

.

3.8.

Cut V-notch in matrix and pull bus wires

from matrix. Cut and remove center

matrix.

Do not cut bus wire strands.

117mm

(4-5/8”)

Bus Wire

Primary Insulation

Ground Lead

Matrix

Ground Lead

Ground Lead

Ground Lead

Black Matrix

Matrix

PCS-COM In-line and T-Splice Kit

12/10 AWG

Crimp

Advertising