Installation procedures, End termination for flx-bc with braid only. 4.5 – Thermon PCS-COM User Manual
Page 6
Advertising
5
3.9.
Apply a liberal amount of RTV sealant to
cable.
3.10.
Slide boot onto the end of the cable.
4.1.
Slide the metallic braid back from the end
of the cable and cut off 38mm (1.5”) of
cable.
38mm
(1.5”)
Metallic Braid
Cable
4.2.
Apply RTV sealant liberally over the end of
the cable and inside the end cap.
4.3.
Slide the end cap onto the cable.
4.4.
Slide the metallic braid over the end cap.
Twist the ends of the metallic braid
together.
End Termination for FLX-BC with Braid only.
4.5.
Slide 8 AWG crimp connector over end of
braid, then crimp to secure braid.
Metallic Braid
Metallic Braid
Metallic Braid
Metallic Braid
8 AWG Crimp
Connector
76mm
(3”)
Cable
ET-8 End Cap
ET-8` End Cap
INSTALLATION PROCEDURES