Installation procedures, End termination for flx-bc with braid only. 4.5 – Thermon PCS-COM User Manual

Page 6

Advertising
background image

5

3.9.

Apply a liberal amount of RTV sealant to

cable.

3.10.

Slide boot onto the end of the cable.

4.1.

Slide the metallic braid back from the end

of the cable and cut off 38mm (1.5”) of
cable.

38mm

(1.5”)

Metallic Braid

Cable

4.2.

Apply RTV sealant liberally over the end of

the cable and inside the end cap.

4.3.

Slide the end cap onto the cable.

4.4.

Slide the metallic braid over the end cap.

Twist the ends of the metallic braid
together.

End Termination for FLX-BC with Braid only.

4.5.

Slide 8 AWG crimp connector over end of

braid, then crimp to secure braid.

Metallic Braid

Metallic Braid

Metallic Braid

Metallic Braid

8 AWG Crimp

Connector

76mm

(3”)

Cable

ET-8 End Cap

ET-8` End Cap

INSTALLATION PROCEDURES