Westermo RM-505U-2-E User Manual

Page 30

Advertising
background image

505U Radio Telemetry Module

Page 30

© September 2002

to a PC for configuration, field testing and for factory testing. Communication is via standard RS-
232 signals. The 505U is configured as DCE equipment with the pinout detailed below.

Pin

Name

Dirn

Function

1

-

-

Not Used.

2

RD

Out

Receive Data - Serial Data Output (High = 0, Low = 1)

3

TD

In

Transmit Data - Serial Data Input (High = 0, Low = 1)

4

DTR

In

Data Terminal Ready - used by 505U as a "wake-up" signal

5

SG

-

Signal Ground

6

-

-

Not Used.

7

-

-

Not Used.

8

-

-

Not Used.

9

-

-

Not Used.

The DTR signal must be connected to the 505U to enable communications and “wake up” the
microprocessor. This means that the DTR wire must be connected - the PC does not need to
control DTR. When communications is established, the green LED will light continuously.

The serial port communicates at a baud rate of 4800 baud, 8 bits, no parity, one stop bit.

An example cable drawing for connection to a personal computer is detailed below:

E505 DB9 (M) Connector

Computer DB9 (F) Connector

1

1

Not Used - optional

2

2

Receive Data

3

3

Transmit Data

4

4

DTR

5

5

Signal Ground

6

6

Not Used - optional

7

7

Not Used - optional

8

8

Not Used - optional

9

9

Not Used - optional