SECTION 3 BYPASSING & ISOLATING

3---1

Figure 3–1. Status lights and Engine Control.

TRANSFER SWITCH

CONNECTED TO NORMAL

CONNECTED TO EMERGENCY

Lower red light is on if

Transfer Switch is on

Emergency.

Upper green light is on

if Transfer Switch is on

Normal.

Figure 3–2. Status lights for Transfer Switch main

contact position.

TS CONNECTED

Upper amber light

should be on.

TS TEST

TS ISOLATED

Figure 3–3. Status lights for Transfer Switch isolation

contact position.

BYPASSING THE ATS*

This procedure explains how to Bypass the closed

transfer switch contacts. Bypassing is required before the

Transfer Switch can be tested or isolated. The Bypass

Switch Handle must be in the OPEN position (green

window indicator) and the Isolation Handle must be in

the CONN [connected] position (window indicator). The

TS Connected light must be on. See Figures 3–1, 3–2, 3–3.

You can only bypass to the same source

that the Transfer Switch is connected.

Solenoid interlock prevents incorrect operation.

1. Observe which Transfer Switch Connected To light is

on (Normal or Emergency) on the door. This is the
position of the transfer switch (see Figure 3–2).

2. Follow the directions on next page to Bypass to the

same source as connected to transfer switch (select
Normal or Emergency).

Window indicator

shows green

when the ATS is

not bypassed.

Window indicator

shows yellow

when ATS is

bypassed to

Emergency.

Window indicator

shows yellow

when ATS is

bypassed to

Normal.

Figure 3–4. Bypass Handle and

three position window indicators.

NOTE:

The 7ATB contains mechanical (window)

indicators for the bypass switch and transfer switch

positions in addition to the LED status lights.

Allowable Positions of the Bypass Switch

in relation to Positions of the Transfer Switch

(with Isolation Handle in the Conn [connected]

position and TS Connected light on)

Transfer Switch

Bypass Switch

can be in either

If Transfer Switch is in

Normal position.

Open or

Normal

If Transfer Switch is in

Emergency position.

Open or

Emergency