Bypassing & isolating – Emerson 7ADTB User Manual

Page 14

Advertising
background image

BYPASSING & ISOLATING

(continued)

3---5

RETURN TO SERVICE

This procedure explains how to return the automatic

transfer switch (ATS) to service after inspection and

maintenance. Observe the Bypass Switch Position indica-

tor and lights).

1. Use the two tab handles to roll the transfer switch

into the enclosure (isolation contacts facing inward)
until the crank bearings stop against the draw–in
plates. Then push in both side rails and close the
enclosure door.

right rail

left rail

tab

handles

Figure 3–15.Transfer switch isolated

and pulled out for inspection.

Close the enclosure door to prevent personal

injury in case of electrical system fault.

2. Turn Isolation Handle clockwise (approx. 6 turns) until

the window shows TEST and TS TEST light comes on.

E

L

N

Turn crank

clockwise

until

window

shows

TEST.

Automatic Transfer Switch

Bypass Switch

Figure 3–16. ISOLATE to TEST position.

TS CONNECTED

Middle amber light

should come on.

TS TEST

TS ISOLATED

position

window

TEST

clockwise – draws in

the transfer switch

Figure 3–17. Isolation Handle turned to TEST.

3. The ATS can be tested now without load interruption

(see page 2–1).

Solenoid interlock prevents you from closing

the isolation contacts until the ATS is in the

same position as the Bypass Switch.

4. Observe which Bypass Switch Position window indica-

tor is yellow (NORMAL or EMERGENCY) at the
Bypass Switch Handle. This indicates the source
connected to the load.

5. Observe which Transfer Switch Connected To light is

on (Normal or Emergency) on the door. This is the
position of the Transfer Switch. If it is not in the same
position as the Bypass Handle change the position of
the Transfer Switch as follows:

To change the position of transfer switch

Operate to NORMAL Operate to EMERGENCY

Turn Transfer Control

switch to Retransfer

Delay Bypass.

Turn Transfer Control

switch to Transfer Test

(hold 15 seconds).*

Connected To Normal

light should come on.

Connected To Emergency

light should comes on.

* If Feature 2B time delay is used, there will be a delay

before transfer to Emergency.

NOTE

: With Normal available, the automatic transfer

switch will not stay in the emergency position unless

Feature 3A time delay is used (at least 30 seconds).