Board Setup

3-2

CI-9110

3.1.1 Switch Functions


The Regulator assembly is configured by two, eight-switch packages which perform the
functions listed in Table 3-1.

Table 3-1 - Regulator Assembly Switch SW1 & SW2 Functions & Settings

Switch

Label

Switch

Function

Page

Ref.

*

Your Setting

**

Your Notes

SW1-1

R/L % per pulse increment

3-4

SW1-2

R/L % per pulse increment

3-4

SW1-3

R/L % per pulse increment

3-4

SW1-4

R/L % per pulse increment

3-4

SW1-5

R/L % per pulse increment

3-4

SW1-6 Not

Used

None

SW1-7 Not

Used

None

SW1-8 Input

Filter

3-4

SW2-1 Guard

(Dynamic/Static)

3-5

SW2-2

Actuator Output Rate of Change

3-6

SW2-3

Actuator Output Rate of Change

3-6

SW2-4

Actuator Output Rate of Change

3-6

SW2-5

Actuator Output Rate of Change

3-6

SW2-6 Guard

(Active/Inactive)

3-5

SW2-7 Not

Used

None

SW2-8

Analog Input (V or I)

3-2

* Record your switch settings (ON or OFF) here for future reference.
** List your corresponding switch functions or values here.

3.2 ANALOG INPUT MODELS


Initially, it will be necessary to check the position of switches SW1-1 through SW1-5. These
switches must be set to their OPEN positions to properly disable the functions associated
with Raise/Lower models. The other uses of these switches are described under topic 3.3.

Analog models can be set to accept a 4-20 mA or 1-5 V dc signal at the Command Input.
Switch SW2-8 selects these outputs as follows:

SW2-8

Analog Range

Close

4-20 mA dc

Open

1-5 V dc

3.3 RAISE/LOWER INPUT MODELS


Raise/Lower Actuator models can be set for continuous or incremental-type input signals
via switches SW1-1 through SW1-5. The switch positions are shown in Table 3-2. The
switch selections are described as follows: