Board Setup

3-4

CI-9110

The relationship between an ON and OFF pulse time periods are shown by the following
two equations:

1) T on Minimum (sec.) = (.01 SR) + K
2) T off Minimum (sec.) = K

Where:

T on Minimum = Raise, Lower or Guard pulse
T off Minimum = Time between pulses.

S = Incremental step value (Table 3-2)
R = Rate of output change (Table 3-3)
K = .04 sec. with R/L filter active or 0.01 sec. with R/L filter turned

off. See Section 3.6 - "Output Rate of Change."

Table 3-2 - Switch SW1 (1-5), Pulse Increments

SW1-5

SW1-4

SW1-3

SW1-2

SW1-1

Output Change

(nominal, ±15%)

Close Close Close Close Close Disabled
Close Close Open Open Close 0.110%

/

Pulse

Open Close Close Close Open 0.182%

/

Pulse

Open Close Close Open Close 0.365%

/

Pulse

Open Close Open Close Close 0.730%

/

Pulse

Open Close Open Open Close 1.090%

/

Pulse

Open Close Open Open Open 1.280%

/

Pulse

Open Open Close Close Close 1.460%

/

Pulse

Open Open Close Close Open 1.640%

/

Pulse

Open Open Close Open Close 1.830%

/

Pulse

Open Open Open Open Open Continuous

*

* Analog Regulator models must always have these switches

set for Continuous Mode.

3.4 INPUT FILTER


A raise or lower input signal can contain noise pulses of an amplitude sufficient to affect
the output. In these situations, switch SW1-8 can be set to activate an input filter. The
switch positions are given below. For Analog models, this switch must always be set to
OPEN.

SW1-8

Filter Status

Close Active
Open Inactive