Service 5-8 CI-9110

5. DMM #1 should read 4.995 V,

±.01 V


6. If the reading of step 5 is out of tolerance, adjust potentiometer R35 on CPU Board to

correct.


7. Recheck both points and readjust if required.

5.8.2 Current Output Span & Load


The current output circuitry is provided with two calibration adjustments. Potentiometer
R50 is used for span adjustment and R49 for load compensation. For these tests DMM #2
using the current measurement function is connected in series with a 250 ohm resistor load
as shown in Figure 5-3. The pushbutton switch is used to jump the load.

1. Adjust input test circuit for 4.995 V on DMM #1.

2. DMM #2 should read 20 mA. If necessary, adjust pot R50 to correct.

3. Press load pushbutton while observing DMM #2. If current reading increases, adjust

R49 CCW. If reading decreases, turn it CW. Repeat procedure until change is less than
±.02 mA.


4. Final reading should be 20 mA,

±.02 mA. If necessary, reset pot R50 and repeat

procedure.


5. Calibration is complete. Restore unit to normal operating status.

5.9 PCB REFERENCE DRAWINGS


Table 5-1 below provides part numbers and drawing references (Figures 5-4 through 5-7)
for the printed circuit boards provided with the Remote Set Regulator.

Table 5-1 - CPU Board & Termination Board Reference Table

Fig.

Assembly

Part #

Pag

e

5-4

Assembly, Analog Type CPU Board w/ Current Output (12V)

389615-03-0

5-9

5-4

Assembly, Analog Type CPU Board w/ Current Output (24V)

389615-06-4

5-9

5-5

Assembly, Analog Termination Board

389644-01-3

5-9

5-6

Assembly, Raise/Lower Type CPU Board w/ Current Output (12V)

389613-03-7 5-10

5-6

Assembly, Raise/Lower Type CPU Board w/ Current Output (24V)

389613-06-1 5-10

5-7

Assembly, Raise/Lower Termination Board

389616-01-0 5-10