13  Directory of the Parameters in Installer Mode and Expert Mode

SMA Solar Technology AG

112

SI30M-44M-60H-80H-BE-en-30

Operating Manual

234.11 GnErrStpTm

Stop time of the

generator in the event of

an error in hours

(expert mode)

0 h to 24 h

✖ ✓ 1 h

234.12 GnWarmTm

Warm-up time in seconds 5 s to 900 s

✖ ✓ 60 s

234.13 GnRvPwr

Active power of the

generator reverse power

in W (expert mode)

0 W to 5,000 W

One Sunny Island

or single-cluster

system

✖ ✓ 100 W

0 W to 20,000 W

Multicluster

system

100 W

234.14 GnRvTm

Permissible time for

reverse power or reverse

current, in s

(expert mode)

0 s to 900 s

✖ ✓ 30 s

234.15 GnCtlMod

Generator control

(expert mode)
The generator control

limits the consumption of

generator current.

Cur

Fixed threshold for

current limitation

✖ ✓ Cur

CurFrq

Frequency-depen

dent current

limitation

234.20 GnAlSns

Anti-islanding sensitivity

(expert mode)

Low

Low

✖ ✓ Normal

Medium

Medium

Normal

Normal

High

High

234.41 GnCurCtlMod Enable I-Loop in

generator operation

(expert mode, only with

SI6.0H-11 and

SI8.0H-11)
I-Loop enables

generators with

inadequate voltage

regulation to be used in

the system.

Droop

Standard

generator

operation without

I-Loop

✖ ✓ Droop

CurCtl

Current-controlled

generator

operation with

I-Loop

234.42 GnAIFac

Anti-islanding factor in

current-controlled

generator operation with

I-Loop (expert mode)

0.00 to 1.00

✖ ✓ 0.10

No.

Name

Description

Value

Explanation

Default

value