9  Troubleshooting

Operating Manual

SI30M-44M-60H-80H-BE-en-30

47

F 121 InvVtgHi

3

An overvoltage has occurred at

connection AC1 of the master.

Ensure that the Sunny Island is

functional. For this, disconnect all

AC sources and loads from the

Sunny Island and restart the

Sunny Island.

Find the cause of the overvoltage

through measurement and

step-by-step connection of the AC

sources and loads.

W 122 InvVtgHiSlv1

1

An overvoltage has occurred at

connection AC1 of slave 1.

W 123 InvVtgHiSlv2

1

An overvoltage has occurred at

connection AC1 of slave 2.

F 129 InvFrqHi

3

An overfrequency has occurred at

connection AC1 of the master.

Ensure that the Sunny Island is

functional. For this, disconnect all

AC sources and loads from the

Sunny Island and restart the

Sunny Island.

Find the cause of the

overfrequency through

measurement and step-by-step

connection of the AC sources and

loads.

W 130 InvFrqHiSlv1

1

An overfrequency has occurred at

connection AC1 of slave 1.

W 131 InvFrqHiSlv2

1

An overfrequency has occurred at

connection AC1 of slave 2.

F 133 InvFrqLo

3

An underfrequency has occurred

at connection AC1 of the master.

Ensure that the Sunny Island is

functional. For this, disconnect all

AC sources and loads from the

Sunny Island and restart the

Sunny Island.

Find the cause of the

underfrequency through

measurement and step-by-step

connection of the AC sources and

loads.

W 134 InvFrqLoSlv1

1

An underfrequency has occurred

at connection AC1 of slave 1.

W 135 InvFrqLoSlv2

1

An underfrequency has occurred

at connection AC1 of slave 2.

W 137 Derate

1

The master has reduced the battery

charging current due to

overtemperature in the

Sunny Island.

• Clean the fans (see Section 10.7

"Cleaning the Fans", page 77).

• Reduce the total power of the

loads, e.g., by staggering their use

over time.

If the Sunny Island frequently

reduces its power, increase power

by replacing the Sunny Island

with a higher-powered version or

by installing additional

Sunny Island inverters.

W 138 DerateSlv1

1

Slave 1 has reduced the battery

charging current due to

overtemperature in the

Sunny Island.

W 139 DerateSlv2

1

Slave 2 has reduced the battery

charging current due to

overtemperature in the

Sunny Island.

No.

Name

Level Cause

Corrective measures