YASKAWA ELECTRIC SIEP C730600 62B 1000-Series Option SI-ET3 Technical Manual

9 Main Command

9

Main Command

‹

NOP: 00H (No Operation Command)

The NOP command is used for network control. The current state is returned as a response. The command can be used in
all communication phases.

‹

PRM_RD: 01H (Read Parameter Command)

The PRM_RD command is used to read a parameter by specifying the parameter number and the data size.

The command can be used in communication phases 2 and 3. Refer to the drive instruction manual for details of
MEMOBUS/Modbus register numbers.

NOP command

Byte

Command

Description

0

NOP (00H)

Command code

1

WDT

Watchdog data

2

CMD_CTRL

Refer to

Command Control (CMD_CTRL) on page 24

.

3
4

Reserved (0)

Not used

5

x
x

31

NOP Response

Byte

Response

Description

0

NOP (00H)

Command code

1

RWDT

Watchdog data

2

CMD_STAT

Refer to

Command Status (CMD_STAT) on page 24

.

3
4

Reserved (0)

Not used

5

x
x

31

PRM_RD command

Byte

Command

Description

0

PRM_RD (01H)

Command code

1

WDT

Watchdog data

2

CMD_CTRL

Refer to

Command Control (CMD_CTRL) on page 24

.

3
4

NO

MEMOBUS/Modbus register number (Lower)

5

MEMOBUS/Modbus register number (Upper)

6

SIZE

Data size to read [units: byte]
Available setting values are 2, 4, 6, and 8.

7

Reserved (0)

Not used

8

Reserved (0)

9

10

x
x

31