No.

(Addr.

Hex)

Name

Description

Values

F7-15

(03F3)

Communication Speed

Selection

Sets the communication speed

0: 10 Mbps

10: 10 Mbps

100: 100 Mbps

101: 10 (Port 1)/100 Mbps (port 2)

102: 100 (Port 1)/10 Mbps (port 2)

Default: 10

<10>

Range: 10; 100 to
102

<10>

F7-16

(03F4)

Communication Loss

Timeout

Sets the timeout value for communication loss detection in

tenths of a second. A value of 0 disables the connection

timeout.

Example: An entered value of 100 represents 10.0 seconds.

Default: 0.0

Min.: 0.0

Max.: 30.0

H5-11

(043C)

Communications

ENTER Function

Selection

Selects the function for the ENTER command that saves

parameter data to the drive.

0: Parameter changes are activated when ENTER command

is written

1: Parameter changes are activated immediately without use

of ENTER command

Default: 1

Range: 0, 1

<1>

To start and stop the drive with the master device using serial communications, set b1-02 to 3. To control the
drive frequency reference of the drive via the master device, set b1-01 to 3.

<2>

When set to 3, 4, or 5, the drive will continue to operate when a fault is detected. Take safety measures, such as
installing an emergency stop switch.

<3>

Available in drive software versions PRG: 1024 and later.

<4>

Parameter setting value is not reset to the default value when the drive is initialized.

<5>

Cycle power for setting changes to take effect.

<6>

When F7-13 is set to 0, parameters F7-01 to F7-12 must be set, and all IP Addresses (as defined with parameters
F7-01 to F7-04) must be unique.

<7>

When F7-14 is set to 0 or 2, parameter F7-15 must be set.

<8>

Default setting differs depending on drive software version. PRG: 1012 to 1015: 0
PRG: 1016 and later: 1

<9>

Setting range differs depending on drive software version. PRG: 1012 to 1023, Range: 0 to 2
PRG: 1024 and later, Range: 0 to 8

<10>

Setting values differ depending on drive software version. PRG: 1012 to 1015, Default: 0; Range: 0, 10, 100
PRG: 1016 to 1023, Default: 10; Range: 10, 100
PRG: 1024 and later, Default: 10; Range: 10; 100 to 102

Table 7 Option Monitors

No.

Name

Description

Value Range

U6-80

to

U6-83

Online IP Address

IP Address currently available; U6-80 is the most significant

octet

0 to 255

U6-84

to

U6-87

Online Subnet

Subnet currently available; U6-84 is the most significant octet 0 to 255

6 Related Drive Parameters

32