Enter command settings when upgrading the drive, H5-11 and the enter command, 7 modbus tcp/ip messaging – Yaskawa Modbus TCP/IP SI-EM3D/V User Manual

Page 39

Advertising
background image

Table 10 Enter Command Types

Register No.

Description

0900H

Writes data into the EEPROM (non-volatile memory) of the drive and enables the data in RAM at

the same time. Parameter changes remain even if the power supply is cycled.

0910H

Writes data in the RAM only. Parameter changes are lost when the drive is shut off.

Note:

1. Because the EEPROM can be written to a maximum of 100,000 times, refrain from writing to the

EEPROM too often. The Enter command registers are write-only. Consequently, if these registers

are read, then the register address will be invalid (Error code: 02H). An Enter command is not required

if reference or broadcast data are sent to the drive.

2. Parameter data cannot be written to EEPROM during undervoltage, even using 0900H.
3. If undervoltage occurs when a making several parameter changes issued with a single ENTER

command, the writing process may be aborted before all of the new changes have been written.

Because all of the data has not yet been written, the EEPROM data error “CPF06” will be displayed

the next time power to the drive is cycled. To prevent this problem, wait approximately 5 seconds

after issuing the ENTER command before shutting off drive power.

u

Enter Command Settings when Upgrading the Drive

When replacing earlier Yaskawa drive models with a V1000 and keeping the MEMOBUS/

Modbus communications settings, parameter H5-11 needs to be set in accordance with how

the Enter command functions in the older drive. H5-11 determines if an Enter command is

needed to activate parameter changes in the drive.
• Set parameter H5-11 to 0 when upgrading from a G7 or F7 series drive to V1000-Series

drive.

• Set parameter H5-11 to 1 when upgrading from a V7 series drive to V1000-Series drive.

n

H5-11 and the Enter Command

H5-11 Settings

H5-11 = 0

H5-11 = 1

Drive being replaced

G7, F7

V7

How parameter settings

are enabled

When the Enter command is received from

the master.

As soon as the value is changed.

Upper/lower limit check

Upper/lower limit check is performed taking

the settings of related parameters into

account.

The upper/lower limit of the changed

parameter is checked only.

Default value of related

parameters

Not affected. The settings of related

parameters remain unchanged. They must

be changed manually if needed.

The default settings of related parameters

are changed automatically.

Error handling when

setting multiple

parameters

Data is accepted even if one setting is

invalid. The invalid setting will be

discarded. No error message occurs.

Error occurs if only one setting is invalid.

All data sent are discarded.

7 Modbus TCP/IP Messaging

YASKAWA TOEP YAICOM 17A V1000 Option Dual-Port Modbus TCP/IP SI-EM3D/V Installation Manual

39

Advertising
This manual is related to the following products: