AO17 Display

Units

Description
parameter n012 or GPD506 parameter n011

2-39

rpm

Specifies number of motor poles (P). Speed is calculated by :
N

s

= 120*f / P.

40 - 3999

custom

Specifies desired reading at maximum output frequency,
where the lower 3 digits indicate the unscaled reading and the
upper digit places the decimal point. The output frequency
range is linearly converted to this new range. For example:

If the display range is desired to be 0.0 – 14.7, AO17 is set to
1147.



This object configures the drive as described below:

Object

ID

Object Name

GPD505

Parameter

GPD506

Parameter

Units Default

Min

Max

AO17

Operator Display Mode

n024

n023

-

0

0

3999

4.1.10 Power Loss Ride-Through – AO18

This analog output defines how the drive will react to a momentary power loss, as described below:

AO18 Ride-Through

Mode

0 Ride-Through

Disabled

1

Ride-Through Enabled for up to 2 seconds

2

Ride-Through Enabled indefinitely, provided control
power is maintained



This object configures the drive as described below:

Object

ID

Object Name

GPD505

Parameter

GPD506

Parameter

Units Default

Min

Max

AO18

Power Loss Ride-Through

n051

n055

-

0

0

2

4.1.11 General Purpose Setup – AO22, AO23

Two analog outputs are defined for setting any drive parameter:

AO22 - Specifies the drive parameter to be set. Writing to this object initiates the write sequence.

AO23 - Specifies the value to be written to the specified parameter. Writing to this object completes the

write sequence and causes the value to be sent to the drive.


Refer to the appropriate Technical Manual for a detailed description of all parameters.

NOTE: The increment listed in the Technical Manual must be considered when specifying a value.

For example, to set GPD506 parameter n070 (GPD505 n066), DC Injection Time at Stop, to 1
second,
AO23 must be set to 10, since the increment for this parameter is 0.1 seconds.