3 stop running, 4 fault, 3 stop – Yaskawa GPD505 User Manual

Page 22: Running

Advertising
background image

TM4028

7/12/2001

22

4.4.3 Stop Running

In this mode, Cable Loss Timeout (AO19) is set to the desired interval and Cable Loss Speed (AO20) is set
to 0. If the time between messages exceeds the timeout interval, the drive’s speed command (AO1) is set
to 0 and the run command (BO1) is set to ‘Off’. Communication Fault Enable (BO10) must be set to ‘Off’.

4.4.4 Fault

In this mode, Cable Loss Timeout (AO19) is set to the desired interval and Communication Fault Enable
(BO10) is set to ‘On’. If the time between messages exceeds the timeout interval, an ‘EF0’ fault is declared
and the drive stops. Cable Loss Speed (AO20) is ignored.

Advertising
This manual is related to the following products: