Diagnostics & Troubleshooting 6 - 14

Table 6.2 Alarm Displays and Processing (continued)

Digital

Operator Display

Description

Cause

Corrective Action

UV2

CTL PS Undervolt

Control Power Supply Undervoltage
Undervoltage of the control circuit when
running.

External load was pulling down
the Drive’s power supplies, or
there was an internal short in the
power/gate Drive board.

Cycle power to the Drive.

Repair or replace the Power PCB/
Gate Drive PCB.

Remove all control wiring and
test Drive.

UV3

MC Answerback

Soft Charge Circuit Fault
The pre-charge contactor opened while the
Drive was running.

Contacts on the soft charge
contactor were dirty and the soft
charge contactor does not
function mechanically.

Cycle power to the Drive.

Check the condition of the soft
charge contactor.

Repair or replace the Power PCB/
Gate Drive PCB.