Start-Up 4 - 14

Parameter

No.

Parameter Name

Digital Operator Display

Description

Setting

Range

Factory

Setting

Control Method

V/F

V/F

w/

PG

OLV

FV

F1-21

<3021>

PG Constant 2
PG Pulse / Rev 2

Sets the number of pulses for the encoder (pulse generator) for
each full rotation of Motor 2.

0 to 60000

1024

No

Q

No

Q

F1-22

<3021>

PG Rotation 2
PG Rotation Sel 2

Determines the direction of rotation for the encoder (PG) con-
nected to Motor 2.
0: Phase A leads with Forward Run Command.
(Phase B leads with Reverse Run Command.)
1: Phase B leads with Forward Run Command.
(Phase A leads with Reverse Run Command.)

0, 1

0

No

Q

No

Q

H4-02

Terminal FM Gain Setting
Terminal FM Gain

Sets terminal FM output voltage (in percent of 10Vdc) when
selected monitor is at 100% output.

0.0 to

1000.0

100.0%

Q

Q

Q

Q

H4-05

Terminal AM Gain Setting
Terminal AM Gain

Sets terminal AM output voltage (in percent of 10Vdc) when
selected monitor is at 100% output.

0.0 to

1000.0

50.0%

Q

Q

Q

Q

L1-01

Motor Overload Protection
Selection
MOL Fault Select

Sets the motor thermal overload protection (OL1) based on the

cooling capacity of the motor.

0: Disabled
1: Standard Fan Cooled (<10:1 motor)
2: Standard Blower Cooled (10:1 motor)
3: Vector Motor (1000:1 motor)

0 to 1

1

Q

Q

Q

Q

L3-04

Stall Prevention Selection
During Decel
StallP Decel Sel

When using a braking resistor, use setting “0”. Setting “3” is used
in very specific applications.
0: Disabled - The Drive decelerates at the active deceleration rate.

If the load is too large or the deceleration time is too short, an
OV fault may occur.

1: General Purpose - The Drive decelerates at the active

deceleration rate, but if the main circuit DC bus voltage reaches
the stall prevention level (380/760 Vdc), deceleration will stop.
Deceleration will continue once the DC bus level drops below
the stall prevention level.

2: Intelligent - The active deceleration rate is ignored and the Drive

decelerates as fast as possible w/o hitting OV fault level.
Range: C1-02/10.

3: Stall Prevention w/ Braking Resistor

0 to 3

1

Q

Q

Q

Q