Parameters A - 29

H4-02

Terminal FM Gain Setting
Terminal FM Gain

Sets terminal FM output level when selected monitor is at 100%.

0.0 to

1000.0

100.0%

Q

Q

Q

Q

H4-03

Terminal FM Bias Setting
Terminal FM Bias

Sets terminal FM output level when selected monitor is at 0%.

–110.0 to

110.0

0.0%

A

A

A

A

H4-04

Terminal AM Monitor
Selection
Terminal AM Sel

Selects which monitor will be the output on terminals AM and FC.
Same function choices as H4-01.

1 to 45

3

A

A

A

A

H4-05

Terminal AM Gain Setting
Terminal AM Gain

Sets terminal AM output voltage (in percent of 10Vdc) when
selected monitor is at 100% output.

0.0 to

1000.0

50.0%

Q

Q

Q

Q

H4-06

Terminal AM Bias Setting
Terminal AM Bias

Sets terminal AM output voltage (in percent of 10Vdc) when
selected monitor is at 0% output.

–110.0 to

110.0

0.0%

A

A

A

A

H4-07

Terminal FM Signal Level
Selection
FM Level Select 1

Selects the signal level of terminal FM.
0: 0 to 10Vdc
1: -10 to +10Vdc
2: 4 to 20mA*

0 or 2

0

A

A

A

A

H4-08

Terminal AM Signal Level
Selection
AM Level Select 2

Selects the signal level of terminal AM.
0: 0 to 10Vdc
1: -10 to +10Vdc
2: 4 to 20mA*

0 or 2

0

A

A

A

A

Serial Communications Setup

H5-01

Drive Node Address
Serial Comm Adr

Selects Drive station node number (address) for Modbus terminals
R+, R-, S+, S-. The Drive’s power must be cycled for the setting to
take effect.

0 to 20

Hex

1F

A

A

A

A

H5-02

Communication Speed
Selection
Serial Baud Rate

Selects the baud rate for Modbus terminals R+, R-, S+ and S-. The
Drive’s power must be cycled for the setting to take effect.
0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19200 bps

0 to 4

3

A

A

A

A

H5-03

Communication Parity
Selection
Serial Com Sel

Selects the communication parity for Modbus terminals R+, R-, S+
and S-. The Drive’s power must be cycled for the setting to take
effect.
0: No Parity
1: Even Parity
2: Odd Parity

0 to 2

0

A

A

A

A

H5-04

Stopping Method After
Communication Error
Serial Fault Sel

Selects the stopping method when a communication timeout fault
(CE) is detected.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only

0 to 3

3

A

A

A

A

H5-05

Communication Fault
Detection Selection
Serial Flt Dtct

Enables or disables the communications timeout fault (CE).
0: Disabled - A communication loss will not cause a

communication fault.

1: Enabled - If communication is lost for more than 2 seconds, a CE

fault will occur.

0 to 1

1

A

A

A

A

H5-06

Drive Transmit Wait Time
Transmit WaitTIM

Set the delay time from when the Drive receives data to when the
Drive sends data.

5 to 65

5ms

A

A

A

A

H5-07

RTS Control Selection
RTS Control Sel

Enables or disables “request to send” (RTS) control:
0: Disabled - RTS is always on
1: Enabled - RTS turns on only when sending

0 to 1

1

A

A

A

A

H5-10

<3021>

Unit Selection for
MEMOBUS Register 0025H
MEMOBUS 25H UNIT

Selects the units used for MEMOBUS registry 0025H (monitors the
output voltage reference).
0: 0.1 V units
1: 1 V units

0, 1

0

A

A

A

A

Pulse I/O Setup

H6-01

Terminal RP Pulse Train Input
Function Selection
Pulse Input Sel

Selects the function of pulse train terminal RP.
0: Frequency reference
1: PID feedback value
2: PID setpoint value

0 to 2

0

A

A

A

A

H6-02

Pulse Train Input Scaling
Pulse In Scaling

Sets the number of pulses (in Hz) that is equal to the maximum
output frequency E1-04.

1000 to

32000

1440Hz

A

A

A

A

H6-03

Pulse Train Input Gain
Pulse Input Gain

Sets the output level when the pulse train input is at 100% as a
percentage of maximum output frequency E1-04.

0.0 to

1000.0

100.0%

A

A

A

A

Denotes that parameter can be changed when the Drive is running.