Parameters a - 15, Table a.1 f7 parameter list (continued) – Yaskawa F7 Drive User Manual User Manual

Page 180

Advertising
background image

Parameters A - 15

E1-04

Maximum Output
Frequency
Max Frequency

These parameters are only applicable when V/F Pattern Selection is
set to Custom (E1-03 = F or FF). To set V/F characteristics in a
straight line, set the same values for E1-07 and E1-09. In this case,
the setting for E1-08 will be disregarded. Be sure that the four
frequencies are set in the following manner or else an OPE10 fault
will occur:

E1-04

≥ E1-11 ≥ E1-06 > E1-07 ≥ E1-09

Note: Setting parameter E1-01=0 is also acceptable

Varies

by

Duty

Rating*

60.0Hz

Q

Q

Q

Q

E1-05

Maximum Output Voltage
Max Voltage

0.0 to
255.0

(240V)

0.0 to
510.0

(480V)

230.0V

or

460.0V

Q

Q

Q

Q

E1-06

Base Frequency
Base Frequency

0.0 to
400.0

60.0Hz

Q

Q

Q

Q

E1-07

Mid Output Frequency A
Mid Frequency A

0.0 to
400.0

3.0Hz

A

A

A

-

E1-08

Mid Output Voltage A
Mid Voltage A

0.0 to
255.0

(240V)

0.0 to
510.0

(480V)

12.6

Vac

or

25.3

Vac

A

A

A

-

E1-09

Minimum Output Frequency
Min Frequency

0.0 to
400.0

0.5Hz

Q

Q

Q

A

E1-10

Minimum Output Voltage
Min Voltage

0.0 to
255.0

(240V)

0.0 to
510.0

(480V)

2.3

Vac

or

4.6

Vac

A

A

A

-

E1-11

Mid Output Frequency B
Mid Frequency B

Set only when the V/F pattern is finely adjusted in the constant
power (HP) area above base speed. Adjustment is not normally
required.

0.0 to
400.0

0.0Hz

A

A

A

A

E1-12

Mid Output Voltage B
Mid Voltage B

0.0 to
255.0

(240V)

0.0 to
510.0

(480V)

0.0Vac

A

A

A

A

E1-13

Base Voltage
Base Voltage

Set only when the V/F pattern is finely adjusted in the constant
power (HP) area above base speed. Adjustment is not normally
required. If E1-13 = 0.0, then value in E1-05 is used for E1-13.
Auto-Tuning sets this value.

0.0 to
255.0

(240V)

0.0 to
510.0

(480V)

0.0Vac

A

A

Q

Q

Denotes that parameter can be changed when the Drive is running.

* For Heavy Duty (HD) Rating: Setting Range=40.0 to 300.0. For Normal Duty (ND) Rating: Setting Range=40.0 to 400.0.

Table A.1 F7 Parameter List (Continued)

Parameter

No.

Parameter Name

Digital Operator Display

Description

Setting

Range

Factory

Setting

Control Method

V/F

V/F

w/PG

Open

Loop

Vector

Flux

Vector

Output voltage (V)

Frequency (Hz)

E1-09 E1-07 E1-06 E1-11 E1-04

E1-05

E1-12

E1-13

E1-08

E1-10