Yaskawa AC Drive Z1000 AC Drive HVAC Fan User Manual

Page 130

Advertising
background image

No.

Name

Setting Range

Default

o1-10

User-Set Display Units Maximum Value

1 to 60000

Determined by

o1-03

n

o1-11: User-Set Display Units Decimal Display

Determines how many decimal points should be used to set and display the frequency reference.

No.

Name

Setting Range

Default

o1-11

User-Set Display Units Decimal Display

0 to 3

Determined by

o1-03

Setting 0: No Decimal Point
Setting 1: One Decimal Point
Setting 2: Two Decimal Points
Setting 3: Three Decimal Points

n

o1-13 to o1-15: Frequency Reference and Frequency Related Monitor Custom Units 1 to 3

Sets the customer specified unit display for the frequency reference parameters and frequency related monitors when o1-03

is set to 3 and o1-09 is set to 15 as custom units.
The custom units consist of three characters selected from o1-13 to o1-15. Each character is selected by ASCII code from

30Hex to 7AHex.

No.

Name

Setting Range

Default

o1-13

Frequency Reference and Frequency Related Monitor Custom Units 1

30H to 7AH

41H

o1-14

Frequency Reference and Frequency Related Monitor Custom Units 2

o1-15

Frequency Reference and Frequency Related Monitor Custom Units 3

n

o1-16, o1-17: F1/F2 Key Function Selection

The HOA Keypad multi-function keys F1 and F2 can be set for different HVAC specific functions. Selects the functions of

the F1/F2 keys and the LCD display text above the F1/F2 keys.

Note:

Parameters o1-16 and o1-17 cannot be set to the same value (except for setting 0).

No.

Name

Setting Range

Default

o1-16

F1 Key Function Selection

0 to 4

0

o1-17

F2 Key Function Selection

0

Setting 0: Standard
Setting 1: Monitor
Setting 2: Drive/Bypass (DRV/BYP)
Setting 3: Bypass Run (RUN BYP)
Setting 4: Toggle Relay Output (RLY)

n

o1-18, o1-19: User-Defined Parameter Upper/Lower

Allows the user to set values that can be used as reference information.

No.

Name

Setting Range

Default

o1-18

User-Defined Parameter Upper

0 to 999

0

o1-19

User-Defined Parameter Lower

1.10 o: Operator-Related Settings

130

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual