D.2 Communication Specifications

Metasys N2 specifications appear in the following table:

Item

Specifications

Interface

RS-485

Communication Parameters

Communication Speed: 9600 bps

Data Length: 8-bit (fixed)

Parity: None

Stop Bit: 1-bit (fixed)

Protocol

Metasys N2

Max Number of Drives

255 per N2 Network Segment