H3-09: terminal a2 signal level selection, H3-10: terminal a2 function selection – Yaskawa AC Drive Z1000 AC Drive HVAC Fan User Manual

Page 93

Advertising
background image

H3-01 = 0

10 V

5 V

0 V

Gain = 200 %

100 %

Frequency
reference

Bias = 0 %

E1-04

Figure 1.50 Frequency Reference Setting by Analog Input with Increased Gain

• Gain H3-03 = 100%, bias H3-04 = -25%, terminal A1 as frequency reference input:

An input of 0 Vdc will be equivalent to a -25% frequency reference.
When parameter H3-01 = 0, the frequency reference is 0% between 0 and 2 Vdc input.

0

2.0 V

10 V

100 %

Frequency
reference

-25%

H3-01 = 0

H3-01 = 1

H3-01 = 0

Analog Input

Voltage

Figure 1.51 Frequency Reference Setting by Analog Input with Negative Bias

n

H3-09: Terminal A2 Signal Level Selection

Selects the input signal level for analog input A2. Set Jumper S1 on the terminal board accordingly for a voltage input or

current input.

No.

Name

Setting Range

Default

H3-09

Terminal A2 Signal Level Selection

0 to 3

2

Setting 0: 0 to 10 V with Zero Limit

The input level is 0 to 10 Vdc. Negative input values will be limited to 0.

Refer to Setting 0: 0 to 10 V with Zero Limit on

page 92

.

Setting 1: 0 to 10 V without Zero Limit

The input level is 0 to 10 Vdc. Negative input values will be accepted.

Refer to Setting 1: 0 to 10 V without Zero Limit on

page 92

.

Setting 2: 4 to 20 mA Current Input

The input level is 4 to 20 mA. Negative input values by negative bias or gain settings will be limited to 0%.

Setting 3: 0 to 20 mA Current Input

The input level is 0 to 20 mA. Negative input values by negative bias or gain settings will be limited to 0%.

n

H3-10: Terminal A2 Function Selection

Determines the function assigned to analog input terminal A2.

Refer to Multi-Function Analog Input Terminal Settings on

page 94

for a list of functions and descriptions.

No.

Name

Setting Range

Default

H3-10

Terminal A2 Function Selection

0 to 26

0

1.7 H: Terminal Functions

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual

93

1

Parameter Details