S6: Z1000 Protection

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

S6-01

(3236)

Emergency Override

Speed

E Override Speed

Sets the speed command used in Emergency Override mode when

S6-02 = 0.

Default: 0.00

Hz

Min.: 0.00

Max.: 240.00

153

S6-02

(3237)

Emergency Override

Reference Selection

E OverrideRefSel

0: Use S6-01 Ref

1: Use AUTO Ref

Selects the frequency reference source for the Emergency

Override function (H1-oo= AF or B0).

0: Use S6-01 Reference

1: Use AUTO Reference

Note:

The Emergency Override inputs will function even

if the CALL alarm is displayed.

Default: 0

Range: 0, 1

153

S6-03

(3238)

ov2 Detect Time

ov2 Detect Time

Sets the detection time of ov2 in 0.1 s increments.

Default: 10.0 s

Min.: 0.0

Max.: 1200.0

153

S6-07

(323C)

Output Phase Loss

Detection Level for

Dynamic Audible Noise

Control

Outp Ph Loss Lv1

Sets the output phase loss detection level for Dynamic Audible

Noise Control. Decrease the setting in steps of 10% when output

phase loss is detected erroneously. This setting rarely needs to be

changed.

Default:

100.0%

Min.: 10.0

Max.: 100.0

153

A.13 S: Special Application

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual

229

A

Parameter List