Yaskawa AC Drive Z1000 AC Drive HVAC Fan User Manual

Page 142

Advertising
background image

n

S3-08: Secondary PI Integral Limit Setting

Sets the maximum output possible from the integrator.

No.

Name

Setting Range

Default

S3-08

Secondary PI Integral Limit Setting

0.0 to 100.0%

100.0%

n

S3-09: Secondary PI Output Upper Limit

Sets the maximum output possible from the secondary PI controller.

No.

Name

Setting Range

Default

S3-09

Secondary PI Output Upper Limit

0 to 100.0%

100.0%

n

S3-10: Secondary PI Output Lower Limit

Sets the minimum output possible from the secondary PI controller.

No.

Name

Setting Range

Default

S3-10

Secondary PI Output Lower Limit

-100.00 to 100.00

0.00%

n

S3-11: Secondary PI Output Level Selection

Sets the secondary PI controller output direction.

No.

Name

Setting Range

Default

S3-11

Secondary PI Output Level Selection

0 or 1

0

Setting 0: Normal Output (Direct Acting)
Setting 1: Reverse Output (Reverse Acting)

n

S3-12: Secondary PI Disable Mode

Selects the secondary PI controller output when disabled.

No.

Name

Setting Range

Default

S3-12

Secondary PI Disable Mode

0 to 2

0

Setting 0: No Output (0%)
Setting 1: Lower Limit (S3-10)
Setting 2: Setpoint

n

S3-13: Secondary PI Low Feedback Detection Level

Sets the secondary PI low feedback detection level.

No.

Name

Setting Range

Default

S3-13

Secondary PI Low Feedback Detection Level

0.00 to 600.00

<1>

0.00

<2>

<1> Upper limit is S3-02, decimal place holder is determined by S3-03.
<2> Unit is determined by S3-04.

1.11 S: Special Parameters

142

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual

Advertising