KACO blueplanet 1502x User Manual

Page 13

Advertising
background image

blueplanet Installation Instructions 1502x - 5002x

Page 13

230.82.6: The type of equipment connected to the

supply is listed, with subsection six identifying solar

electric systems as permissible.

All components within a UL 1741 compliant inverter

must pass evaluation spacing, voltages and currents

that the inverter is rated for. The UL 508 standard,

industrial control equipment, auxiliary devices has

provisions for testing manually operated switches. The

integrated switch passed the UL508 standard under the

file E304888 for use within a UL 1741 approved grid tied

inverter. The switch was tested 6000 operating cycles at

the nominal AC and DC voltages and currents as noted

in table one below. Additional operating cycles of 4000

resulted in a total of 10000 successful operating cycles.

The switch was de constructed and evaluated under a

pass fail criteria.

As referenced in the NEC, subsection 690.17, the switch

must meet applicable voltage and current ratings. The

AC and DC switch ratings are detailed in this table:

AC / DC

Disconnect

Inverter Models

1502x

2502x

3502x

5002x

DC Nominal

Voltage: V

DC

600

550

550

550

550

DC Nominal

Current: I

DC

21.45

21.45

21.45

40

40

AC Nominal

Voltage: V

AC

240/

208

240/

208

240/

208

240/

208

240/

208

AC Nominal

Current: I

AC

8

8

12.5

17

24

The GFDI fuse is located on the bottom plate of the

inverter. When a ground fault occurs this fuse will open

causing the inverter to shut down and indicate a fault.

Replace only with the same type and rating fuse. The

fuse is a fast-acting 600 V

DC

/ 1 A KLKD1 (manufacturer:

littlefuse) rated device.

The night time start switch is located on the bottom

plate of the inverter. Press and hold the start switch for

up to 5 seconds to wake the inverter when there is no

DC input voltage. This allows the user to display the

power that was produced during that day.

Section 5 ·

Installation and Start-Up

Advertising