B) connecting the s0 output, C) the rs485 interface connection, 8 starting up the inverter – KACO blueplanet 1502x User Manual

Page 20: Important, Action

Advertising
background image

Page 20

blueplanet Installation Instructions 1502x - 5002x

(B) Connecting the S0 output

The inverter is equipped with an S0 pulse output. Items

such as a large display can be connected to it. The pulse

rate is adjustable (see section 5.9, “Parameter program-

ming”).

(C) The RS485 interface connection

The connection terminal (Figure 5.15) is on the blue-

planet communication circuit board. To connect sev-

eral blueplanet inverters, terminal A of one blueplanet

is connected to terminal A of the other blueplanet.

Terminal B is connected in the same manner. A twisted,

shielded data cable is required for this. The connec-

tion to the KACO proLOG is established similarly to the

interconnection of inverters. A connection diagram is

displayed in figure 5.21. The total length of the RS485

wiring should not exceed 4,000 feet. Proper polarity

must be maintained or devices will not be able to com-

municate.

Figure 5.16: Connection diagram for the RS485 interface using

the KACO proLOG

In figure 5.15, a terminating resistor (R

a

) is connected to

the last inverter in the chain. For proper signal transmis-

sion, the last unit in a chain must have a terminating

resistor.

The terminating resistors in the other inverters of the

chain must be deactivated (set to “OFF”). In the last unit

of the chain, switch “1” is set to “ON” and switch “2” is

set to “OFF”. The switch is on the communication circuit

board above the terminal block (Figure 5.14).

With a bus system such as the RS485, each unit shar-

ing this bus must possess a unique address, regardless

of whether it is an inverter or any other device. The

exception is the monitoring device which is the master.

This unit does not need an address. For inverters, the

address range can be selected between 1 and 32. You

can define the address for each inverter using the con-

figuration menu (see Operating Instructions).

IMPORTANT

Ensure that the A and B wires are properly connec-

ted. Communication is not possible if the wires are

reversed.

5.8 Starting up the inverter

After completing the mechanical and electrical installa-

tion, the inverter is put into operation as follows:

NOTE

The inverter can be put into operation only under

daylight conditions (i.e. at a solar generator voltage

of > 100 V). If no daylight or solar generator voltage

is present, the inverter can be activated by pressing

the night start key if there is AC voltage present (see

section 4.4 in the Operating Instructions). However,

normal operation is not possible in this condition.

Only the values can be read off the display.

ACTION

- Assure voltage supply

- Switch on the external AC/DC disconnect switch

(O

I).

During the initial start-up, the corresponding country

and language must be selected. Select the appropriate

language using the ‘2’ (right) key, press the ‘1’ (left) key

to advance to the country selection. Press the ‘2’ key

to advance through the various grid types. Once the

proper grid type is selected press the ‘1’ key then press

both the ‘1’ and ‘2’ keys at the same time to save the

settings. If the improper grid settings were selected,

hold down the ‘2’ key to start the process again.

Section 5

· Installation and Start-Up

NOTE

If the power is cycled or 10 minutes elapse the set-

tings for the grid type are locked and a password will

need to be obtained from tech support.

The top green LED “OK” lights when DC voltage is

available and indicates that it is ready to be put into

operation. The display now indicates the current PV

generator voltage “Start from xx V, meas.: xxx V”. If the

measured voltage is greater than the starting voltage,

the unit will start grid-feeding after a country-specific

waiting time. This start-up waiting period is required in

order to ensure that the generator voltage is continu-

ously above the power delivery limit of 125 V (1502x) and

200 V (2502x, 3502x, and 5002x).

A quick start routine is provided for startup and test

purposes. This routine circumvents the start-up delay

period. This quick start routine is found in the configu-

ration mode menu (see Operating Instructions).

During the normal start-up procedure, the line relays

audibly switch on after a country-specific waiting time

and the feeding of the grid starts. This is indicated by

the middle green LED with the house and power line

symbol next to it. The display now shows the power

being fed into the grid. Key ‘1’ (left) can now be used

to display the various measured values (see Operating

Instructions section 4.4).

blueplanet

proLOG

AA BB

blueplanet

AA BB

blueplanet

AA BB

AB

DSL or

Ethernet

120V

AC

Max. 32 inverters

Advertising
This manual is related to the following products: