blueplanet Installation Instructions 1502x - 5002x

ACTION

Before connecting the PV generator to the bluepla-

net, check that the PV generator is not grounded.

– Measure the DC voltage between the protective

ground (PG) and the positive lead and between

the protective ground (PG) and the negative lead

of the PV generator.

– If stable voltages can be measured, this indicates

a ground fault in the PV generator or its wiring.

The ratio between the measured voltages gives an

indication as to the location of this fault. Rectify

this fault before taking any further measurements.

– Measure the electrical resistance between the

protective ground (PG) and the positive lead and

between the protective ground (PG) and the nega-

tive lead of the PV generator.

– Low resistance (< 2 MΩ) indicates a high-impe-

dance ground fault of the PV generator, which

must be fixed prior to continuing with the instal-

lation.

ACTION

The ground for the DC input is provided by the inte-

gral GFDI circuit. DC input should not be grounded

external to the unit.

Circuit board fuse

The power section has two internal circuit board fuses.

These are labelled F801 or F861 on the circuit board.

F801:

Model: 179120 5x20 time-lag 250 V

AC

/ 0.4 A

Manufacturer: SIBA

F861:

Model: TR5-Fuse series 372 250 V

AC

/ 125 V

DC

/ 1 A time-lag

Manufacturer: Littelfuse/Wickmann

!

WARNING

For continued protection against risk of fire, replace only with

same type and ratings of fuse.

Positive Grounded System

NOTE

In this configuration the Positive of the PV generator

is grounded through the GFDI fuse.

'&

'&

39



'&

39



'&

39

*)',

39

39



39



*)',

39



39



Negative

Positive

Figure 5.5 DC connection 3502x / 5002x series - Positive
Grounding System

NOTE

A screwdriver (slotted, 3.5 mm) is to be used for the

terminals in the inverter. Put the screwdriver into the

intended cut-out. Press the screwdriver upwards a

bit. Put the cable into the spring terminal. Put the

screwdriver back into the original position. Remove

the screwdriver. The spring terminal is closed and

the cable is held in place. Lightly pull on the wire to

be sure it is secure.

!

CAUTION

Be sure the inverter is configured for the proper DC grounding

configuration of the system.

!

CAUTION

The voltage of the solar generator must be measured before

connecting the DC leads to the inverter terminals. The DC vol-

tage must not exceed the max. generator voltage because this

would destroy the unit.

Section 5 ·

Installation and Start-up