6 electrical connection, A) grid connection, Warning – KACO blueplanet 1502x User Manual

Page 18

Advertising
background image

Page 18

blueplanet Installation Instructions 1502x - 5002x

Figure 5.13: AC-connection

AC Connections are a 3 or 4 wire connection. In 4 wire

systems incorporating a Neutral there will be the follow-

ing connections; Line-1, Line-2, Neutral, and Ground. In

3 wire systems not incorporating a Neutral there will be

the following connections; Line-1, Line-2, and Ground.

We recommend the following conductor cross-sections

for cable lengths up to 60 feet:

– blueplanet 1502x: AWG 12 up to AWG 4

75°C Copper Wire

– blueplanet 2502x: AWG 12 up to AWG 4

75°C Copper Wire

– blueplanet 3502x: AWG 12 up to AWG 4

75°C Copper Wire

– blueplanet 5002x: AWG 8 up to AWG 4

75°C Copper Wire

Larger cross-sections should be used for longer leads.

NOTE

Use Copper Conductors only.

The following AC over-current protection must be used

for the installation of the inverter.

– blueplanet 1502x

→ 15 A Breaker

– blueplanet 2502x

→ 20 A Breaker

– blueplanet 3502x

→ 25 A Breaker

– blueplanet 5002x

→ 30 A Breaker

5.6 Electrical connection

General information

The electrical connections can be established after the

inverter is installed in its fixed location. Knockouts are

provided on the sides, bottom, and rear to easily run

conduit to the desired locations.

NOTE

Only conduit pipes according to UL 514 B can be used.

!

WARNING

Inputs and output circuits of this unit are isolated from the

enclosure. System grounding must be done in accordance with

the National Electrical Code (NEC), ANSI/NFPA 70 and is the

responsibility of the installer.

You must adhere to all mandatory safety regulations,

the currently required technical connection specifica-

tions of the responsible power supply company, as well

as to other generally applicable regulations.

!

WARNING

To connect the inverter, the AC and DC sides must be discon-

nected from all power sources and secured against being

inadvertently energized.

(A) Grid Connection

AC- connection

(see Figure 5.13)

Figure 5.12: Connection of the blueplanet

Section 5 ·

Installation and Start-Up

/13(

N L1 L2 PE

Advertising
This manual is related to the following products: