Installation 12, Nomenclature – Emerson Precision Cooling For Business-Critical Continuity Figure i User Manual

Page 16

Advertising
background image

Installation

12

Figure 10 Three-phase, 3-5 ton model schematic, typical

3

2

4

1

L1

L2

L3

27

27,29,30

HP1

C1

HG1

W

BL

BR

1

4

2

3

BK

CHTR

BR

BR

R

BK

HP2

R

BK

RHTR1

RHTR2

HG1

HGSV

LLSV1

BR R OR

T3T2T1

COMP

R

BK

Y

CAP2

BR

1C1

2C1

3C1

BR

BR

F1

F2

TX1

BK

BK

Conductors Field-Supplied
(See Note 5)

HGBP Signal
Output
Connection

EVAPORATOR UNIT

Unit Alarm
Input
Connection

Earth Ground
By Others

3-Phase Line
Voltage Supply
By Others
(See Note 3)

OUTDOOR CONDENSING MODULE

See Note 7

See Note 1

See Note 6

24V Power
Supply
From Unit
Min 40VA

24V Ground

'FM'

Fan

Motor

1. Transformer 'TX1' provided on units with nameplate voltages greater
than 240V.
2. Use copper conductors onl y. See unit nameplate for main supply wire
sizing data. Wire per local codes.
3. A remote disconnect switch is to be field supplied and mounted
within sight of the condensing unit. See unit nameplate for voltage
and amperage requirements.
4. All motors have internal line break overload protectors. Three-phase
motors protected for primary single-phasing conditions.
5. Terminals 1, 2, 3 and 4 are for connection of control circuit from evaporator
unit. Wiring by others to be NEC Class 2 and sized for 1 volt maximum drop.
6. Wire '1' is connected to the grounded side of the 24V Class 2 circuit.
7. Receiver heater No.2 'RHTR2' supplied on 4- and 5-ton standard models and
3/3.5-ton high ambient and Quiet-Line models.

NOMENCLATURE

Standard Devices
C1 -- Condenser Contactor
CAP2 -- Fan Motor Capacitor
CHTR -- Compressor Heater
COMP -- Compressor
F1 -- Transformer Fuse 1
F2 -- Transformer Fuse 2
FM -- Fan Motor
HP1 -- High Pressure Switch
(Auto Reset)
HP2 -- Pressure Switch Receiver
(Auto Reset)

Optional Devices
HG1 -- Hot Gas Relay
HGSV -- Hot Gas Solenoid Valve

Factory-Supplied Line Voltage
Field-Installed Line Voltage Wiring
Optional Line Voltage Wiring
Factory-Supplied 24V NEC Class 2 Wiring
Optional 24V Wiring
Factory-Supplied 24V NEC Class 2 Wiring
Factory-Supplied Earth Grounding Wire
Pigtail Leads 24V Wiring
Terminal Strip Connection

OR - Orange
R - Red
BR - Brown
P - Purple
GN - Green

Y - Yellow
BL - Blue
BK - Black
W - White

WIRE COLOR CODE

Insulation Color

GN / Y

Tracer Color

191643
Rev. 0

LLSV -- Liquid Line Solenoid Valve
RHTR1 -- Receiver Heater No. 1
RHTR2 -- Receiver Heater No. 2
(3-,4-,and 5-ton only)
TX1 -- Transformer Line

Voltage to230V

Grounding Lug Connection