2.5.6 General System Charge Requirements

Liebert split system units are designed with quick-connect fittings and are factory-charged to proper

levels. Due to the wide range of operating ambients and sensitivity of the system components to

charge level, the system charge must be maintained at recommended levels.
If there is any doubt that the system has the correct refrigerant charge level, the correct

procedure is to remove the entire system charge, evacuate the system and weigh in the

recommended factory charge total for both units and any line sets or field piping.
Tables 7
, 8, 11 and 12 are included for field piping allowances, condensing unit charges, line sets and

evaporator charges.

Total refrigerant charge = evaporator + lines + condensing unit

NOTE
All condensing units and most evaporator units are fully charged with refrigerant. Some

evaporator units are shipped from the factory with a nitrogen holding charge only. (Refer to

evaporator serial tags.) If field-supplied refrigerant piping is installed, refrigerant must be

added to the system. Refer to Figure 12 for field-supplied piping guidelines.

Table 12

Evaporator Charge Levels

Indoor Unit

Evaporator

Models

Charge R-407C

oz (kg)

Liebert

Mini-Mate2

MMD11/12E

3 (0.085)

MMD17/18E

4 (0.113)

MMD23/24E

7 (0.198)

MMD35/36E

7 (0.198)

MMD59/60E

4 (0.113)

MMD95/96E

7 (0.198) each circuit

Liebert DataMate

DME020E

4 (0.113)

DME027E

5 (0.141)

DME037E

6.5 (0.184)

Liebert Challenger

3000

BF/BU036E

9 (0.255)

BF/BU060E*

13 (0.368)

* Evaporator is charged with nitrogen at the factory