7 electrical data, Electrical data, Table 16 – Emerson Precision Cooling For Business-Critical Continuity Figure i User Manual

Page 26: Table 17

Advertising
background image

Installation

22

2.7

Electrical Data

Table 16

Electrical data—Standard sound and ambient models (95°F/35°C) 60Hz

Model #

Nominal

Capacity

Tons

* Electrical

Characteristic

Input Voltage- Phase

208/230-1

208/230-3

460-3

575-3

14

1

FLA

8.4

WSA

10.2

OPD

15

20

1.5

FLA

12.1

WSA

14.8

OPD

25

27

2

FLA

13.5

WSA

16.5

OPD

25

37

3

FLA

19.3

12.8

6.4

5.9

WSA

23.8

15.7

7.8

7.1

OPD

40

25

15

15

42

3.5

FLA

15.3

7.1

6.6

WSA

18.8

8.7

8.0

OPD

30

15

15

67

5

FLA

24.1

11.7

9.1

WSA

29.3

14.2

11.1

OPD

45

20

15

96

8

FLA

35.6

17.4

13.5

WSA

40.8

19.9

15.4

OPD

60

25

20

* FLA = Full Load Amps

WSA = Wire Size Amps (minimum supply circuit current capacity)
OPD = Overcurrent Protection Device (fuse or circuit breaker)

Table 17

Electrical data—High ambient models (105°F/41°C) 60Hz

Model #

Nominal

Capacity,

Tons

* Electrical

Characteristic

Input Voltage-Phase

208/230-1

208/230-3

460-3

575-3

37

3

FLA

21.3

14.8

7.4

5.9

WSA

25.8

17.7

8.8

7.1

OPD

40

25

15

15

42

3.5

FLA

17.3

8.1

6.6

WSA

20.8

9.7

8.0

OPD

30

15

15

67

5

FLA

24.2

11.7

9.3

WSA

29.4

14.2

11.3

OPD

50

20

15

* FLA = Full Load Amps

WSA = Wire Size Amps (minimum supply circuit current capacity)
OPD = Overcurrent Protection Device (fuse or circuit breaker)
Model # 14, 20 and 96 are not available in high ambient versions.