Table 18, Electrical data—quiet-line models (95°f/35°c) 60hz, Table 19 – Emerson Precision Cooling For Business-Critical Continuity Figure i User Manual

Page 27: Table 20

Advertising
background image

Installation

23

Table 18

Electrical data—Quiet-Line models (95°F/35°C) 60Hz

Model #

Nominal

Capacity

Tons

* Electrical

Characteristic

Input Voltage-Phase

208/230-1

208/230-3

460-3

575-3

27

2

FLA

13.0

WSA

16.0

OPD

25

37

3

FLA

18.8

12.3

6.4

5.2

WSA

23.3

15.2

7.8

6.4

OPD

40

25

15

15

42

3.5

FLA

14.8

6.9

5.9

WSA

18.3

8.5

7.3

OPD

30

15

15

67

5

FLA

21.1

10.9

8.8

WSA

25.9

13.4

10.8

OPD

45

20

15

* FLA = Full Load Amps

WSA = Wire Size Amps (minimum supply circuit current capacity)
OPD = Overcurrent Protection Device (fuse or circuit breaker)
Model # 14, 20 and 96 are not available in Quiet-Line versions.

Table 19

Electrical data—Standard sound and ambient models (95°F/35°C) 50Hz

Model #

Nominal

Capacity

Tons

* Electrical

Characteristic

Input Voltage-Phase

220-1

200/230-3

380/415-3

13

1

FLA

9.9

19

1.5

FLA

10.9

26

2

FLA

12.7

4.9

36

3

FLA

18.4

7.0

41

3.5

FLA

15.3

8.5

66

5

FLA

24.1

13.2

95

8

FLA

20.3

* FLA = Full Load Amps

Table 20

Electrical data—High ambient models (105°F/41°C) 50Hz

Model #

Nominal

Capacity

Tons

* Electrical

Characteristic

Input Voltage-Phase

220-1

200/230-3

380/415-3

13

1

FLA

19

1.5

FLA

26

2

FLA

14.8

6.0

36

3

FLA

20.5

13.1

41

3.5

FLA

19.8

9.6

66

5

FLA

24.2

13.2

95

8

FLA

* FLA = Full Load Amps