Figure 12 Refrigerant piping diagram

Table 5

Pipe length and condenser elevation relative to evaporator

Nominal

System Size

Tons

Max. Equiv.

Pipe Length

ft. (m)

Maximum PFH

Level Above

Evaporator, ft. (m)

Maximum PFH

Level Below

Evaporator, ft. (m)

1 or 1.5

50 (15)

40 (12)

15 (4.6)

2

100 (30)

40 (12)

15 (4.6)

3, 3.5, 5 or 8

150 (45)

50 (15)

15 (4.6)

Table 6

Equivalent lengths for various pipe fittings, ft (m)

Copper Pipe

OD, in.

90 Degree

Elbow Copper

90 Degree

Elbow Cast

45 Degree

Elbow

Tee

Gate

Valve

Globe

Valve

Angle

Valve

1/2

0.8 (0.24)

1.3 (0.39)

0.4 (0.12)

2.5 (0.76)

0.26 (0.07)

7.0 (2.13)

4.0 (1.21)

5/8

0.9 (0.27)

1.4 (0.42)

0.5 (0.15)

2.5 (0.76)

0.28 (0.08)

9.5 (2.89)

5.0 (1.52)

3/4

1.0 (0.3)

1.5 (0.45)

0.6 (0.18)

2.5 (0.76)

0.3 (0.09)

12.0 (3.65)

6.5 (1.98)

7/8

1.45 (0.44)

1.8 (0.54)

0.8 (0.24)

3.6 (1.09)

0.36 (0.1)

17.2 (5.24)

9.5 (2.89)

1-1/8

1.85 (0.56)

2.2 (0.67)

1.0 (0.3)

4.6 (1.4)

0.48 (0.14)

22.5 (6.85)

12.0 (3.65)

1-3/8

2.4 (0.73)

2.9 (0.88)

1.3 (0.39)

6.4 (1.95)

0.65 (0.19)

32.0 (9.75)

16.0 (4.87)

1-5/8

2.9 (0.88)

3.5 (1.06)

1.6 (0.48)

7.2 (2.19)

0.72 (0.21)

36.0 (10.97)

19.5 (5.94)

Refrigerant trap = Four times equivalent length of pipe per this table

Evaporator

Evaporator

Condensing
Unit

Condensing
Unit

NOTE
When installing remote condensing units below the
evaporator, the suction gas line should be trapped with
an inverted trap to the height of the evaporator . This
prevents refrigerant migration to the compressors
during off cycles . Maximum recommended vertical
level drop to condensing unit is 15 ft. (4.6m) .

Pitch down 1/2" (13mm) per 10 ft. (3m)

Suction Line Piping
Condensing Unit Above Evaporator
Traps recommended at the base of riser
exceeding 5 ft (1.5m) and every 20 feet
(6m) of vertical rise.

Suction Line Piping
Condensing Unit
Below Evaporator

See Table 5 for maximum

vertical rise recommendation

above evaporator.

NOTE

When installing remote condensing units below the

evaporator, the suction gas line should be trapped

with an inverted trap to the height of the evaporator.

This prevents refrigerant migration to the compres-

sors during off cycles. Maximum recommended verti-

cal level drop to condensing unit is 15 ft. (4.6m).