Index

Troubleshooting

RESETTING THERMOSTAT
The thermostat can be reset back to factory default programs and configuration options. Removing power from the thermostat will
not
reset it to the default settings. Before resetting the thermostat you may want to make note of the previously selected configura-
tion options and programming.

To reset the thermostat, press and release PROGRAM

RUN

, then press the

FAN

, TIME

BACK

and

buttons at the

same time. This will reset the thermostat to factory default programs and configuration. The display will momentarily go
blank, and then all segments on the display will momentarily be shown. The thermostat will then go into the AUTO HOLD
mode and will maintain a factory preset temperatures of 62

°

F in Heat or 85

°F in Cool

. To clear the HOLD TEMPERA-

TURE overide press the PROGRAM

RUN

button.

TROUBLESHOOTING

POSSIBLE CAUSE

1. Blown fuse or tripped circuit
breaker.
2. Furnace power switch to OFF.
3. Furnace blower compartment
door or panel loose or not properly
installed.

CORRECTIVE ACTION

Replace fuse or reset breaker.

Turn switch to ON.
Replace door panel in proper position to engage
safety interlock or door switch.

SYMPTOM

No Heat/No Cool/No Fan
(common problems)