Fig.3, Operation – Sealey SSC11003 User Manual

Page 4

Advertising
background image

4.2. ROOM TEMPERATURE.

4.2.1. for correct functioning of the compressor the room

temperature must not be lower than 5°c or higher than 45°c.

4.2.2. If the compressor is operated at a room temperature

lower than the minimum value, the condensate could be

separated within the circuit resulting in water mixing with the

oil. the resulting deterioration in oil quality would fail to

guarantee the even formation of an effective lubricating film

between moving parts with the possibility of seizure.

4.2.3. If the compressor works at a room temperature higher than

maximum value, the compressor would take in air that is too

hot, which would prevent the heat exchanger from adequately

cooling the oil in the circuit, raising the working temperature of

the machine, thus causing the thermal safety device to trip,

which stops the compressor due to the excessive temperature

of the air/oil mixture at the screw outlet.

4.2.4.

The maximum temperature of the room is to be measured

while the compressor is running.

4.3. OPERATING ENVIRONMENT.

the compressor must be installed in a large room that is well-

ventilated, dust-free and sheltered away from rain and frost.

the compressor takes in a large amount of air that is required

for internal ventilation. A dusty atmosphere would in time

cause damage and inefficient performance. Dust drawn into

the machine will be taken into the air filter causing it to clog

rapidly. Incoming dust will also settle onto the components and

will be blown against the cooling radiator, consequently

compromising the efficiency of the heat exchanger. It is

therefore obvious that the cleanliness of the area in which the

compressor is installed is crucial for the optimum efficiency of

the machine, avoiding excessive running and maintenance

costs. to facilitate maintenance and to create a favourable

circulation of air, the compressor must have sufficient free

space all around it as shown in fig.2.

4.4. UNSUITABLE ENVIRONMENTAL CONDITIONS.

4.4.1.

DO NOT install the compressor in an environment where there

is a risk of fire and/or explosion.

4.4.2.

DO NOT install the compressor in an environment where there

is a risk that the machine may overheat. (maximum permitted

operating temperature 45ºc).

4.4.3.

DO NOT install the compressor in an atmosphere where the

humidity will be higher than 80%.

4.4.4.

NOTE: this compressor is designed to work with a tank of a

specific size i.e.100ltr. no liability will be accepted for any

related malfunctions or problems resulting from the

compressor being connected to a different tank. the

compressor should not be modified in any way.

Original Language Version

4.5. CONNECTING TO THE TANK COMPRESSED AIR OUTLET.

connect the compressor to the air delivery system using the

quick coupler (fig3.A). use hose of the same diameter (or

greater) as the compressor outlet. If a connection hose leaks

or is faulty never try to repair it but replace with a sound one.

fig.3

fig.3

5. OPERATION

WARNING! Ensure that you have read, understood and

apply Section 1 safety instructions.

NOTE:

take care when selecting tools for use with the

compressor. Air tool manufacturers normally express the

volume of air required to operate a tool in cubic feet per minute

(cfm). this refers to free air delivered by the compressor (‘air

out’) which varies according to the pressure setting. Do not

confuse this with the compressor displacement which is the air

taken in by the compressor (‘air in’). ‘Air out’ is always less

than ‘air in’ due to losses within the compressor.

5.1. INITIAL START.

5.1.1.

Upon first use or following an extended inactive period switch

on and off (fig3.E.) for 3 or 4 seconds several times. This is to

start the oil circulating.

5.1.2. Switch the machine back on with the drain tap (fig.4) open

and run for 2 minutes to circulate the oil thoroughly without

building pressure.

5.1.3. close the drain tap and re-start the compressor; allow to build

up to full pressure at which point the pump will unload and run

idle for 2 minutes.

5.1.4. If there has been no air use during this 2 minutes, the machine

will shut down to stand-by mode.

5.1.5. When the pressure drops by 2 bar, the machine will switch on

again to regain full pressure.

5.1.6: It is not necessary to repeat this procedure in normal use.

A: Air line quick connector

B: Pressure regulator

C: Tank pressure gauge

D: Line pressure gauge

E: On/Off switch

F: Hours counter

G: Reset button

fig.4

5.2. PRESSURE REGULATION.

5.2.1. The tank pressure is shown by gauge fig.3.c.

5.2.2. The line (delivery) pressure is shown by gauge fig

.3.D. and is

adjusted by means of the pressure regulator fig.3.B.

to increase pressure: turn clockwise; to decrease: turn

anticlockwise.

5.2.3.

NOTE: the regulator should be turned back to zero before

running the machine for the first time, and the pressure

increased to the desired level when the tank is full. failure to

do this could result in damage to the diaphragm within the

regulator.

5.3. SWITCHING OFF

5.3.1. Switch off using on/off switch (fig.3.E)

DO NOT switch off by

switching the mains supply off.

5.3.2. When switched off by the on/off switch, the compressor will

continue to run for some time in order to clear the pump of oil.

5.4. DUTY CYCLE

the recommended duty cycle is 80%, meaning that the

machine should not be run continuously for more than

48 minutes in one hour.

ssc11003 Issue: 1 - 03/05/13

© Jack sealey Limited

Advertising