Mechanical Considerations

10

Figure 9

Overall dimensions with removable coupling

4.2

Determining Placement in the Conditioned Space

Refer to site-specific drawings for exact placement. Efficient cooling of the rack equipment depends on

proper placement of equipment, proper use of blanking plates in any voids in the rack, and good cable

management.
The Liebert XDR is engineered to fit the rear of computer enclosure cabinets. Figures 7, 8 and 9

illustrate the module's dimensions and the location of pipes.
Ensure that there is 25.6" (649mm) clearance in the rear to allow the door to open fully.

1-1/2"

(38mm)

1-5/16"

(33mm)

1-1/2"

(38mm)

78-3/8"

(1991mm)

80"

(2032mm)

5-7/8"

(149mm)

20-1/2"

(520mm)

110deg

23-1/2" (597mm)

7/8"

(22mm)

27-3/8" (695mm)

6-1/2"

(165mm)

2-1/8"

(54mm)

25-5/8"

(651mm)

27-3/8" (695mm)

Piping is not load-bearing and

should never be used to lift or

move the Liebert XDR.