1 basics, Dvanced, Icroprocessor – Emerson Liebert Deluxe System/3 DH User Manual

Page 26: With, Raphics, Ontrol, Etup, Basics, Figure 3, Advanced microprocessor with graphics control

Advertising
background image

Advanced Microprocessor with Graphics Control Setup

18

4.0

A

DVANCED

M

ICROPROCESSOR

WITH

G

RAPHICS

C

ONTROL

S

ETUP

The Advanced Microprocessor with Graphics (AG) Control for your Deluxe unit features an easy-to-

use, menu-driven LCD Graphics Display. The menus, control features, and circuit board details are

described in this section. For more details on the control refer to 5.0 - Response by Control Type—

Advanced Microprocessor Controls; for details on the alarms refer to 6.0 - Alarm Descriptions

and Solutions.

4.1

Basics

Control keys include ON/OFF, Menu/ESCape, ENTER, Increase (up) arrow, and Decrease (down)

arrow. Refer to Figure 3. These keys are used to move through the menus as prompted on the LCD

display Figure 4.
To turn the unit on, press the ON/OFF key after power is applied. To turn the unit off, press the ON/

OFF key before power is disconnected.
Active alarms are indicated on the LCD screen by a ringing bell graphic. Alarms are also annunciated

by an audible beeper. To silence an alarm, press the ENTER key as prompted on the display. The unit

stores the 60 most recent alarms for review.
Setpoints, DIP switch settings, and other selections were made on your unit after testing at the fac-

tory and are kept in nonvolatile memory. Setpoints were chosen based on typical operating experi-

ence. Other selections were made based on options included with your unit. Make adjustments to the

factory default selections ONLY if they do not meet your specifications. When entering setpoints, time

delays, etc., the allowable ranges are displayed and may require a password, if enabled.