Installation, Unpacking, Panel mounting – Precision Digital PD603 User Manual

Page 10

Advertising
background image

Sabre P Model PD603 Process Meter

Instruction Manual

10

INSTALLATION

There is no need to remove the meter from its case to com-
plete the installation, wiring, and setup of the meter.

Unpacking

Remove the meter from box. Inspect the packaging and con-
tents for damage. Report damages, if any, to the carrier.
If any part is missing or the meter malfunctions, please contact
your supplier or the factory for assistance.

Panel Mounting

Prepare a standard 1/8 DIN panel cutout – 3.622" x 1.772" (92 mm
x 45 mm). Refer to Mounting Dimensions, page 29 for more details.

Clearance: allow at least 4" (102 mm) behind the panel for wiring.

Panel thickness: 0.04" - 0.25" (1.0 mm - 6.4 mm).
Recommended minimum panel thickness to maintain Type 4X
rating: 0.06" (1.5 mm) steel panel, 0.16" (4.1 mm) plastic panel.

Remove the two mounting brackets provided with the meter (back-off
the two screws so that there is ¼" (6.4 mm) or less through the
bracket. Slide the bracket toward the front of the case and remove).

Insert meter into the panel cutout.

Install mounting brackets and tighten the screws against the panel.
To achieve a proper seal, tighten the mounting bracket screws
evenly until meter is snug to the panel along its short side. DO NOT
OVER TIGHTEN, as the rear of the panel may be damaged.

Panel

Gasket

Mounting

Bracket

Mounting

Screw

Removable

Connectors

3.622" (92mm)

1.772"

(45mm)

Panel Cutout

to DIN 43700

Square Corners to 0.060"

(1.5mm) Max Radius

A

B

Tolerances:
A: +0.032 (+0.8mm)
-0.000 (-0.0mm)
B: +0.024 (+0.6mm)
-0.000 (-0.0mm)

Figure 1. Panel Cutout and Mounting

Advertising