Riello UPS Sentinel Dual (High Power) (3.3 - 10 kVA) User Manual

Page 53

Advertising
background image

53

U

SE





4. Use 3-pole cables with 4 mm

2

section. With reference to the

figure shown at the side:

- Insert the cable from the 32A magneto-thermal switch into

cable guide P1 (input line).

- Insert the cable from the load into cable guide P2 (output

line).

- Strip the cables observing the measurements provided.

- Insert the stripped end in the terminals provided.






5. Connect the wires to the relative terminals strictly following the instructions set out below:

Input line

a - Ensure that the magneto-thermal switch

upstream is open.

b - Connect the earth wire to terminal 3.

c - Connect the neutral wire to terminal 1.

d - Connect the phase wire to terminal 2.

Output line

a - Connect the earth wire to terminal 4.

b - Connect the neutral wire to terminal 5.

c - Connect the phase wire to terminal 6.

6. Ensure that a jumper is connected at

terminals 7 and 8; this is needed for the
correct operation of the UPS.

7. Secure the cable guides to the flange, close the drawer and secure it with the screw removed previously.



A WARNING LABEL MUST BE AFFIXED TO ALL MAINS POWER ISOLATING SWITCHES INSTALLED FAR FROM THE
UPS AREA, IN ORDER TO REMIND SUPPORT SERVICE PERSONNEL THAT THE CIRCUIT IS CONNECTED TO A UPS. THE
LABEL MUST CARRY THE FOLLOWING MESSAGE:

ISOLATE THE UNINTERRUPTIBLE POWER SYSTEM (UPS)

BEFORE WORKING ON THIS CIRCUIT

P1

P2

B y - P a s s

M a n u t e n z i o n e R em oto

Remote Maintenance

By-Pass

1

2

3

4

5

6

7

8

Advertising