Roblem solving – Riello UPS Sentinel Dual (High Power) (3.3 - 10 kVA) User Manual

Page 64

Advertising
background image

64

P

ROBLEM SOLVING

Irregular functioning of the UPS is very often not an indication of a fault but due simply to trivial problems,
minor difficulties or carelessness.
We therefore recommend that you refer to the table below which gives a summary of useful information to
solve the most common problems.

PROBLEM

POSSIBLE CAUSE

SOLUTION

THE DISPLAY DOES NOT

SWITCH ON

GENERAL SWITCH NOT

PRESSED

Press the general switch located on the front panel.

THE BATTERY PACK

CONNECTOR IS

DISCONNECTED

Connect the battery pack connector by following the
instructions set out in the paragraph “REPLACING
THE BATTERY PACK”.

NO CONNECTION TO THE

ELECTRICITY MAINS

Check the connection to the electricity mains.

MAINS VOLTAGE FAILURE

(BLACK-OUT)

Check the presence of the electricity mains voltage.

UPSTREAM PROTECTION

TRIGGERED

Reset the protection.
WARNING: Check that there is no overload in output
to the UPS.

THE DISPLAY IS ON BUT

THE LOAD IS NOT

POWERED

THE UPS IS IN STAND-BY

MODE

Press the “ON” key located on the front panel to power
the loads.

STAND-BY OFF MODE HAS

BEEN SELECTED

The mode has to be changed.
The STAND-BY OFF mode (back-up) in fact only
powers the loads in the event of a black-out.

NO CONNECTION TO THE

LOAD

Check the connection to the load.

THE UPS IS OPERATING

FROM BATTERY EVEN

THOUGH THE MAINS

VOLTAGE IS PRESENT

UPSTREAM PROTECTION

TRIGGERED

Reset the protection.
WARNING: Check that there is no overload in output
to the UPS.

THE INPUT VOLTAGE IS

OUTSIDE THE ALLOWED

TOLERANCE FOR

OPERATION FROM MAINS

Problem dependent on the mains. Wait for the input
mains to return within tolerance. The UPS will
automatically go back to operation from mains.

THE UPS DOES NOT

SWITCH ON AND THE

DISPLAY SHOWS ONE OF

THESE CODES: A06, A08

THE TEMPERATURE OF THE

UPS IS LOWER THAN 0°C

Check the temperature of the environment where the
UPS is located; if it is too low, bring it to above the
minimum threshold (0°C).

THE DISPLAY SHOWS THE

CODE: A11

INPUT RELAY BLOCKED

The fault does not cause any particular malfunctions. If
the problem should occur again on a subsequent start-
up, contact the support service centre.