Riello UPS Sentinel Dual (High Power) (3.3 - 10 kVA) User Manual

Page 67

Advertising
background image

67

P

ROBLEM SOLVING

Commands in progress: indicates presence of a remote command in progress.

CODE

DESCRIPTION

C01

Remote shutdown command

C02

Remote load on bypass command

C03

Remote switch-on command

C04

Battery test in progress



LOCK

The LOCK (block) type report signals are usually preceded by an alarm signal and, on account of their
importance, result in the inverter being switched off and the load being powered through the bypass line (the
procedure is excluded in case of lockouts due to strong and persistent overloads and lockouts following a short-
circuit).

CODE

DESCRIPTION

L03

Auxiliary power supply incorrect

L04

High temperature on heat sinks

L05

Temperature Sensor1 broken

L07

Temperature Sensor2 broken

L10

Input fuse broken or input relay stuck (does not close)

L13

Capacitor precharging failure

L20

Capacitor bank undervoltage

L21

Capacitor bank overvoltage

L40

Inverter overvoltage

L41

D-C voltage on output

L42

Inverter voltage not right

L43

Inverter undervoltage

L50

Overload: load > 103%

L51

Overload: load > 110%

L52

Overload: load > 150%

L53

Short-circuit

Advertising