Riello UPS NetMan 204 User Manual

Page 40

Advertising
background image

REGISTER

(1)

UPS - MEASUREMENTS

UNIT

NUMBER ADDRESS

9ч11

8ч10

12

11

Input mains star voltage V1

V

13

12

Input mains star voltage V2

V

14

13

Input mains star voltage V3

V

15

14

Input current phase L1

0.1*A

16

15

Input current phase L2

0.1*A

17

16

Input current phase L3

0.1*A

18

17

Input frequency

0.1*Hz

19ч21

18ч20

22

21

Bypass mains star voltage V1

V

23

22

Bypass mains star voltage V2

V

24

23

Bypass mains star voltage V3

V

25

24

Bypass frequency

0.1*Hz

26

25

Output star voltage V1

V

27

26

Output star voltage V2

V

28

27

Output star voltage V3

V

29ч31

28ч30

32

31

Output current phase L1

0.1*A

33

32

Output current phase L2

0.1*A

34

33

Output current phase L3

0.1*A

35

34

Output peak current phase L1

0.1*A

36

35

Output peak current phase L2

0.1*A

37

36

Output peak current phase L3

0.1*A

38

37

Load phase L1

%

39

38

Load phase L2

%

40

39

Load phase L3

%

41

40

Output active power phase L1

0.1 kW

42

41

Output active power phase L2

0.1 kW

43

42

Output active power phase L3

0.1 kW

44

43

Output frequency

0.1*Hz

45ч47

44ч46

48

47

Battery voltage

0.1*V

49

48

Positive battery voltage

0.1*V

50

49

Negative battery voltage

0.1*V

51

50

Battery current

0.1*A

52

51

Remaining Battery Capacity

%

53

52

54

53

Remaining back-up time

Minutes

55ч58

54ч57

59

58

Total output energy (32 bit)

Least Significant Register

0.1 kWh

60

59

Most Significant Register

61

60

62

61

Internal UPS temperature

°C

63

62

Sensor 1 temperature

°C

64

63

Sensor 2 temperature

°C

65ч72

64ч71

(1)

The register number

n must be addressed n-1 in the data packet.

Some measures may not be available for all the UPS. In this case, the relative register

remains at 0xFFFF value.

- 40 -