Thermo Pride Heat Pump Coil LX-13 User Manual

Page 2

Advertising
background image

2

SECTION II: GENERAL INFORMATION

This instruction covers the installation of the following coils with 80+ or
90+ AFUE furnaces or MA/MX/MV air moving systems.

The coils have sweat connect fittings. All coils are shipped with a low
psi nitrogen holding charge.

INSPECTION

As soon as a coil is received, it should be inspected for possible dam-
age during transit. If damage is evident, the extent of the damage
should be noted on the carrier’s delivery receipt. A separate request for
inspection by the carrier’s agent should be made in writing. See Local
Distributor for more information. Check drain pan for cracks or break-
age.

CLEARANCES

DURING INSTALLATION

Clearance must be provided for:

1.

Refrigerant piping and connections

2.

Maintenance and servicing access - including cleaning the coil

3.

Condensate drain line

4.

Filter removal / change

5.

Removal of coil assembly

FIGURE 1: Component Location - Coil MC & FC

Coil Access
Panel

Suction Line
Connection

Liquid Line
Connection

Alternate Drain Location

Label
Location

Drain Location
Horizontal Application
(on MC Coils Only)

Primary Drain

Secondary Drain

Bottom Door Panel

FIGURE 2: Component Location - Coil PC

Label Location

Coil Access
Panel

Primary Drain

Secondary Drain

Bottom Door Panel

Alternate Drain Locations

Suction Line
Connection

Liquid Line

Connection

TABLE 1: Dimensions - MC Coils

Models

Dimensions

1

1. All dimensions are in inches.

Refrigerant

Connections

2

2. Refrigerant line sizes may require larger lines for extended line lengths. See York bulletin #690.01-AD1V for details.

Height

Width

Opening Widths

Line Size

A

B

C

D

Liquid

Vapor

MC18A

22

14 1/2

13 3/8

13 1/2

3/8

3/4

MC18B

22

17 1/2

16 3/8

16 1/2

MC24A

26 1/2

14 1/2

13 3/8

13 1/2

MC24B

26 1/2

17 1/2

16 3/8

16 1/2

MC30A

26 1/2

14 1/2

13 3/8

13 1/2

MC30B

26 1/2

17 1/2

16 3/8

16 1/2

MC32A

22

14 1/2

13 3/8

13 1/2

MC35B

22

17 1/2

16 3/8

16 1/2

MC35C

22

21

19 7/8

20

MC36A

26 1/2

14 1/2

13 3/8

13 1/2

7/8

MC36B

26 1/2

17 1/2

16 3/8

16 1/2

MC36C

26 1/2

21

19 7/8

20

MC37A

26 1/2

14 1/2

13 3/8

13 1/2

3/4

MC42B

32

17 1/2

16 3/8

16 1/2

7/8

MC42C

32

21

19 7/8

20

MC43B

26 1/2

17 1/2

16 3/8

16 1/2

MC43C

26 1/2

21

19 7/8

20

MC48C

32

21

19 7/8

20

MC48D

32

24 1/2

23 3/8

23 1/2

MC60D

32

24 1/2

23 3/8

23 1/2

MC62D

36

24 1/2

23 3/8

23 1/2

20

3/8”

(Opening)

B

C

3/4” Flange

A

21 1/2”

BOTTOM
OPENING
DIMENSIONS

D

20 1/4”

Advertising