LIMITATIONS

These coils should be installed in accordance with all national and local
safety codes.

SECTION III: COIL METERING DEVICES

An orifice or a TXV to be installed in the field. Refer to installation man-
ual with TXV kit. It is recommended to install the orifice or TXV kit prior
to installation of coil in cabinet and brazing line sets.

Consult the outdoor installation guide for outdoor units that require an
orifice as a metering device for the indoor coil. The orifice and the
Schraeder core are supplied with the outdoor unit. Install Schraeder
core in the suction line Schraeder body and cap with the supplied plas-
tic cap.

TXV METERING DEVICE

Please refer to Technical Guide to verify which TXV is installed in this
coil and that this is a valid system match for the AC or HP unit installed.

The temperature sensing bulb is attached to the coil suction header
line.

TABLE 4: Coil Air Flow Limits

Coil

Size

Outdoor Unit

Tons

CFM Limits

Minimum

Maximum

18

1-1/2

525

675

24

1-1/2

525

675

2

700

900

30, 32

2

700

900

2-1/2

875

1125

35

2-1/2

875

1125

3

1050

1200

36, 37

2-1/2

875

1125

3

1050

1350

42

3

1050

1350

3-1/2

1225

1575

43

3

1050

1350

3-1/2

1225

1575

48

3

1050

1350

3-1/2

1225

1575

4

1400

1800

60, 62, 64

4

1600

1800

5

1750

2250

For models that have factory installed TXV’s, take caution not to
apply high temperatures to the TXV assembly or equalizer line
while brazing.

NOTICE

FIGURE 3: TXV Bulb Installation

FIGURE 4: Proper Bulb Location

COIL UNDER PRESSURE.
Relieve pressure by depressing schrader stem. Coil may have fac-
tory installed TXV or may require orifice or TXV to be added. See
outdoor unit documentation for correct orifice or TXV to be used.
Refer to coil nameplate for orifice or TXV identification for this unit.

The coil should be open to the air for no more than 2 minutes to
keep moisture and contaminates from entering the system. If the
coil cannot be brazed into the refrigeration system in that time, the
ends should be temporarily closed or plugged. For a short term
delay, use masking tape over the ends of the copper tubing to close
the tube to the air. For a longer term delay, use plugs or caps.
There is no need to purge the coil if this procedure is followed.

Vapor
Line

Thermal
Expansion
Valve Bulb

Thermal
Expansion
Valve

Distributor
Body

Liquid
Line

TXV
Equalizer
Line

(Wrapped with

insulation)

TXV BULB
(Cover completely
with insulation)

SCREW

CLAMP

NUT

SUCTION LINE

NOTICE