Notice – Thermo Pride Premiere XT 16 SEER User Manual

Page 4

Advertising
background image

4

The outdoor condensing unit must be connected to the indoor evapora-

tor coil using field supplied refrigerant grade copper tubing that is inter-

nally clean and dry. Units should be installed only with the tubing sizes

for approved system combinations as specified in tabular data sheet.

The charge given is applicable for total tubing lengths up to 15 feet. See

Application Data Part Number 247077 for installing tubing of longer

lengths and elevation differences.

PRECAUTIONS DURING LINE INSTALLATION

1. Install the lines with as few bends as possible. Care must be taken

not to damage the couplings or kink the tubing. Use clean hard

drawn copper tubing where no appreciable amount of bending

around obstruction is necessary. If soft copper must be used, care

must be taken to avoid sharp bends which may cause a restriction.

2. The lines should be installed so that they will not obstruct service

access to the coil, air handling system, or filter.

3. Care must also be taken to isolate the refrigerant lines to minimize

noise transmission from the equipment to the structure.

4. The vapor line must be insulated with a minimum of 1/2" foam rubber

insulation (Armaflex or equivalent). Liquid lines that will be exposed

to direct sunlight and/or high temperatures must also be insulated.

5. Tape and suspend the refrigerant lines as shown. DO NOT allow

tube metal-to-metal contact. See Figure 2 "Tubing Hanger".

6. Use PVC piping as a conduit for all underground installations as

shown in Figure 3 "Underground Installation". Buried lines should be

kept as short as possible to minimize the build up of liquid refrigerant

in the vapor line during long periods of shutdown

7. Pack fiberglass insulation and a sealing material such as permagum

around refrigerant lines where they penetrate a wall to reduce vibra-

tion and to retain some flexibility.

8. See application part number 247077 for additional piping informa-

tion.

PRECAUTIONS DURING BRAZING OF LINES

All outdoor unit and evaporator coil connections are copper-to-copper

and should be brazed with a phosphorous-copper alloy material such

as Silfos-5 or equivalent. DO NOT use soft solder. The outdoor units

have reusable service valves on both the liquid and vapor connections.

The total system refrigerant charge is retained within the outdoor unit

during shipping and installation. The reusable service valves are pro-

vided to evacuate and charge per this instruction.
Serious service problems can be avoided by taking adequate precau-

tions to ensure an internally clean and dry system.

PRECAUTIONS DURING BRAZING SERVICE VALVE

Precautions should be taken to prevent heat damage to service valves

by wrapping a wet rag around it as shown in Figure 4 "Heat Protection".

Also, protect all painted surfaces, insulation, and plastic base during

brazing. After brazing, cool joint with wet rag.

The valve can be opened by removing the plunger cap and fully insert-

ing a hex wrench into the stem and backing out counter-clockwise until

valve stem just touches the chamfered retaining wall.
Connect the refrigerant lines using the following procedure:
1. Refer to the Tabular Data Sheet for proper vapor and liquid line siz-

ing.

Using a larger than specified line size could result in oil return prob-
lems. Using too small a line will result in loss of capacity and other
problems caused by insufficient refrigerant flow. Slope horizontal
vapor lines at least 1" every 20 feet toward the outdoor unit to facili-
tate proper oil return.

FIGURE 2: Tubing Hanger

NOTICE

LIQUID
LINE

INCORRECT

CORRECT

TAPE

SHEET METAL
HANGER

INSULATED
VAPOR LINE

FIGURE 3: Underground Installation

Dry nitrogen should always be supplied through the tubing while it
is being brazed, because the temperature is high enough to cause
oxidation of the copper unless an inert atmosphere is provided. The
flow of dry nitrogen should continue until the joint has cooled.
Always use a pressure regulator and safety valve to insure that only
low pressure dry nitrogen is introduced into the tubing. Only a small
flow is necessary to displace air and prevent oxidation.

This is not a backseating valve. The service access port has a
valve core. Opening or closing valve does not close service access
port.
If the valve stem is backed out past the chamfered retaining wall,
the O-ring can be damaged causing leakage or system pressure
could force the valve stem out of the valve body possibly causing
personal injury.

Do not leave the system open to the atmosphere. Unit damage
could occur due to moisture being absorbed by the POE oil in the
system. This type of oil is highly susceptible to moisture absorp-
tion.

TO INDOOR

COIL

TO OUTDOOR

COIL

CAP

INSULATED
VAPOR LINE

LIQUID
LINE

PVC
CONDUIT

Advertising