Thermo Pride Spirit Gas TG8S Single Stage PSC 80% User Manual

Page 12

Advertising
background image

998491-UIM-B-1013

12

Johnson Controls Unitary Products

SECTION V: ELECTRICAL POWER

ELECTRICAL POWER CONNECTIONS

Field wiring to the unit must be grounded. Electric wires that are field
installed shall conform to the temperature limitation for 63°F (35°C) rise
wire when installed in accordance with instructions. Refer to Table 6 in
these instructions for specific furnace electrical data.

Annual Fuel Utilization Efficiency (AFUE) numbers are determined in accordance with DOE Test procedures.
Wire size and over current protection must comply with the National Electrical Code (NFPA-70-latest edition) and all local codes.
The furnace shall be installed so that the electrical components are protected from water.

SUPPLY VOLTAGE CONNECTIONS

1. Provide a power supply separate from all other circuits. Install over-

current protection and disconnect switch per local/national electrical
codes. The switch should be close to the unit for convenience in
servicing. With the disconnect or fused switch in the OFF position,
check all wiring against the unit wiring label. Refer to the wiring dia-
gram in this instruction.

2. Remove the screws retaining the wiring box cover. Route the power

wiring through the opening in the unit into the junction box with a
conduit connector or other proper connection. In the junction box
there will be 3 wires, a Black Wire, a White Wire. Connect the power
supply as shown on the unit-wiring label on the inside of the blower
compartment door or the wiring schematic in this section. The black
furnace lead must be connected to the L1 (hot) wire from the power
supply. The white furnace screw must be connected to neutral. Con-
nect the power supply ground to the green screw (equipment
ground) An alternate wiring method is to use a field provided 2” (5.1
cm) x 4” (10.2 cm) box and cover on the outside of the furnace.
Route the furnace leads into the box using a protective bushing
where the wires pass through the furnace panel. After making the
wiring connections replace the wiring box cover and screws. Refer
to Figure 16.

3. The furnace's control system requires correct polarity of the power

supply and a proper ground connection. Refer to Figure 16

LOW VOLTAGE CONTROL WIRING CONNECTIONS

Install the field-supplied thermostat by following the instructions that
come with the thermostat. With the thermostat set in the OFF position
and the main electrical source disconnected, connect the thermostat
wiring from the wiring connections on the thermostat to the terminal
board on the ignition module, as shown in Figures 17 or 18. Electronic
thermostats may require the common wire to be connected. Apply
strain relief to thermostat wires passing through cabinet. If air condition-
ing equipment is installed, use thermostat wiring to connect the Y and C
terminals on the furnace control board to the proper wires on the con-
densing unit (unit outside).

The 24-volt, 40 VA transformer is sized for the furnace components
only, and should not be connected to power auxiliary devices such as
humidifiers, air cleaners, etc. The transformer may provide power for an
air conditioning unit contactor.

Use copper conductors only.

Table 6: Ratings & Physical / Electrical Data

Input

Output

Nominal

Airflow

AFU

E

Air Temp.

Rise

Max.

Outlet

Air Temp

Blower

Blower

Size

Max

Over-Current

Protect

Total

Unit

Amps

Min. wire Size

(awg) @ 75 ft

one way

MB

H

kW

MB

H

kW

CFM

m

3

/

min

°F

°C

°F

°C

HP

Amp

s

40

11.7

32

9.4

800

22.7

80.0

25-55

14-31

155

68.3

1/5

2.1

9 x 8

10

4.5

14

60

17.6

48

14.1

1000

28.3

80.0

25-55

14-31

155

68.3

1/3

3.8

9 x 8

10

6.0

14

60

17.6

48

14.1

1200

34.0

80.0

30-60

17-33

170

76.7

1/3

4.8

11 x 8

10

7.0

14

80

23.5

64

18.8

1200

34.0

80.0

35-65

19-36

165

73.9

1/3

4.8

11 x 8

10

7.5

14

80

23.5

64

18.8

1600

45.3

80.0

25-55

14-31

155

68.3

1/2

7.5

11 x 10

15

10.0

14

80

23.5

64

18.8

2200

62.3

80.0

25-55

14-31

155

68.3

1

14.5

11 x 11

20

16.0

12

100

29.3

80

23.4

1200

34.0

80.0

40-70

22-39

170

76.7

1/3

4.8

9 x 8

10

7.5

14

100

29.3

80

23.4

1600

45.3

80.0

35-65

19-36

165

73.9

1/2

7.5

11 x 10

15

10.0

14

100

29.3

80

23.4

2000

56.6

80.0

25-55

14-31

155

68.3

1

14.5

11 x 11

20

17.0

12

120

33.7

96

26.9

1600

45.3

80.0

40-70

22-39

170

76.7

1/2

7.5

11 x 10

15

10.0

14

120

33.7

96

26.9

2000

56.6

80.0

30-60

17-33

160

71.1

1

14.5

11 x 11

20

17.0

12

130

38.1

104

30.5

2000

56.6

80.0

35-65

19-36

165

73.9

1

14.5

11 x 11

20

17.0

12

FIGURE 16: Electrical Wiring

Electrical Entry

Junction
Box

L1-Hot

Neutral

Connect ground
lead to screw

BLK

WHT

The power connection leads and wiring box may be relocated to the
left side of the furnace. Remove the screws and cut wire tie holding
excess wiring. Reposition on the left side of the furnace and fasten
using holes provided.

Set the heat anticipator in the room thermostat to 0.4 amps. Setting it
lower will cause short cycles. Setting it higher will cause the room
temperature to exceed the set points.

Some electronic thermostats do not have adjustable heat anticipa-
tors. They should be set to six cycles per hour. Follow the thermostat
manufacturer's instructions.

Advertising